BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B305358
Premises: 300 20 STREET BROOKLYN BIN: 3017396     Block: 891   Lot: 37
   
Application Completed and Certified

Filed: 300 20 ST Census Tract:   145 Health Area:  4400
1ST,2ND,3RD,4TH Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   307
Related Job Number:    302231270
DOB Cross Street(s):    5 AVENUE,    6 AVENUE
Status:   C - JOB IS SIGNED OFF 04/28/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/13/2008 10:39 AM
Application Entered:   06/13/2008 Job Start Date:   06/13/2008
Last Change:   04/28/2010 Job End Date:   10/30/2008
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     09/17/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011749 Licensee Name: JEROME DALY
Firm: 003344 Firm Name: AMRA ELECTRICAL CORP
Firm Phone: 718-444-5209  Firm Address: 1415 UTICA AVENUE BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $298.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: R&G GOLDEN CONSTRUCTION
Authorized Representative:  TIM FIORE
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  5  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 60  120    30  60     12           
Total Units : 282 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 5 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/13/2008 Notice: 1 - FIRST NOTICE 07/07/2009
Power Issued: 06/13/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B305358
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/29/2009 07/07/2009 JMZ A E (45) (4) Y
INSPECTION COMMENTS: N
 
(2) 08/11/2009 08/17/2009 JMZ J Y (75) (0) Y
INSPECTION COMMENTS: N
 
(3) 09/17/2009 09/18/2009 HMC C R E (10) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B305358
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
GFI SERVICE AND WATER ROOMS
RSLV 06/29/2009 06/29/2009 08/11/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
DRIVEN GROUND RACEWAY NOT CONTINUOUS
RSLV 06/29/2009 06/29/2009 08/11/2009
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BOND ALL RECEPTACLES
RSLV 06/29/2009 06/29/2009 08/11/2009
 
004 (999) OTHER
SERVICE SWITCH WORKSPACE HEIGHT NOT 6FT 6IN 110.26E
RSLV 06/29/2009 08/11/2009 09/17/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.