NYC Department of Buildings
Electrical Application Details for App #: B304485
Premises: 23 DODWORTH STREET BROOKLYN BIN: 3395061     Block: 3229   Lot: 7
   
Application Completed and Certified

Filed: 24 LAWTON ST Census Tract:   393 Health Area:  3200
BASEMENT -ROOF Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11221 Community Board:   304
Special Place Name:   BUSHWICK
Related Job Number:    301860715
DOB Cross Street(s):   BROADWAY,    BUSHWICK AVENUE
Status:   C - JOB IS SIGNED OFF 02/19/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/20/2008 9:12 PM
Application Entered:   05/20/2008 Job Start Date:   05/22/2008
Last Change:   02/19/2010 Job End Date:   11/25/2008
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     01/19/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011014 Licensee Name: GARFIELD MAITLAND
Firm: 002352 Firm Name: MAITLAND ELECTRIC CORP.
Firm Phone: 718-360-9353  Firm Address: 501 EDISON AVENUE BRONX NY 10465 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,230.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE KELESIDEZ
Owner Business Name: 18 LAWTON LLC
Authorized Representative:  GEORGIO TERZIDEZ
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  (1) 600 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  52  (48) #4 RISERS
B. Over #2 to 1/0  2  (2) #1/0
C. Over 1/0 to 250 MCM  2  (1) 1/0, (1) 250MCM
D. Over 250 MCM  7  TO BE DETERMINED
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  48  100 MLO
C. 3 Phase Up to 225 AMPS  3  (2)225AMP, (1)100AMP
D. 3 Phase Over 225 AMPS  1  (1)400AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 220  718  107  293  228     25           
Total Units : 1591 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 48 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/20/2008 Notice: 1 - FIRST NOTICE 10/21/2009
Power Issued: 05/20/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE ENTRANCE, RISERS, BRANCH CIRCUIT WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B304485
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/07/2009 08/10/2009 PAT V G (90) (5) Y
INSPECTION COMMENTS: N
 
(2) 10/15/2009 10/21/2009 DEX V Y E (80) (0) Y
INSPECTION COMMENTS: N
 
(3) 11/30/2009 12/04/2009 FMO J R (55) (0) Y
INSPECTION COMMENTS: OUTLET ON 4TH FL BALCONY TO MOVE OVER CHECK BALCONY GFCI
 
(4) 01/19/2010 01/25/2010 DEX C E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B304485
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL FLOORS BONDING JUMPER FOR RECEPTACLES NOT PROVIDED 250.146
RSLV 08/07/2009 10/15/2009 11/30/2009
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BASEMENT ALL SERVICE SWITCHES
RSLV 08/07/2009 08/07/2009 10/15/2009
 
003 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
APT 6D BALCONY GFCI
RSLV 08/07/2009 08/07/2009 10/15/2009
 
004 ( 30) OUTLET BOXES ARE NOT SECURED
ALL FLOORS OUTLET BOXES UNDER THE A/C/ UNIT
RSLV 08/07/2009 08/07/2009 10/15/2009
 
005 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
BASEMENT PUL BOXES
RSLV 08/07/2009 08/07/2009 10/15/2009