BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B304425
Premises: 111 8 AVENUE BROOKLYN BIN: 3024794     Block: 1068   Lot: 4
   
Application Completed and Certified

Filed: 111 8 AV Census Tract:   165 Health Area:  4500
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
Special Place Name:   PARK SLOPE
DOB Cross Street(s):   PRESIDENT STREET,    CARROLL STREET
Status:   C - JOB IS SIGNED OFF 10/03/2008
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   06/19/2008 Job Start Date:   06/20/2008
Last Change:   10/03/2008 Job End Date:   06/30/2008
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     07/24/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011636 Licensee Name: CARLTON ASPINALL
Firm: 002470 Firm Name: ANOTHER NYCER ELEC. CORP.
Firm Phone: 718-649-0900  Firm Address: 900 E. 92ND STREET BROOKLYN NY 11236 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $130.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE PILGRIM
Owner Business Name: 111-115 APT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS 3PHASE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0 200AMPS 3 PHASE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 11 #4-Wire 0 #10-Wire 0
Existing Meters 11 + New Meters 11 - Removed Meters 0 = Total Meters 22

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/19/2008 Notice:  05/19/2008
Power Issued: 06/19/2008 Response: F - FILED TO REMOVE OBJECTION 06/19/2008

Follow-Up: X - FILED APPL,NOW CLOSED 06/19/2008
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B304425
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/14/2008 05/19/2008 FMO W (5) (5)
INSPECTION COMMENTS: N
 
(2) 07/24/2008 07/28/2008 FMO C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B304425
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
DEFECTIVE WIRING IN END LINE BOX 110.2A
RSLV 05/14/2008 05/14/2008 07/24/2008
 
002 (999) OTHER
A DEFECTIVE END LINE BOX IN USE EQUIPTMENT ROTTED 110.11
RSLV 05/14/2008 05/14/2008 07/24/2008
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO WATER GROUND PROVIDED FOR SERVICE SWITCH 250.24
RSLV 05/14/2008 05/14/2008 07/24/2008
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
END LINE BOX COVER MISSING 314.25
RSLV 05/14/2008 05/14/2008 07/24/2008
 
005 (999) OTHER
B SERVICE SWITCH NEUTRAL NOT BONDED 250.28
RSLV 05/14/2008 05/14/2008 07/24/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order