BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B303424
Premises: 3280 NOSTRAND AVENUE BROOKLYN BIN: 3197604     Block: 7308   Lot: 32
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 3280 NOSTRAND AV Census Tract:   566 Health Area:  8722
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11229 Community Board:   315
DOB Cross Street(s):   AVENUE S,    AVENUE T
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/21/2008 7:49 PM
Application Entered:   04/21/2008 Job Start Date:   04/22/2008
Last Change:   08/22/2025 Job End Date:   08/25/2008
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     04/08/2009      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010102 Licensee Name: GEORGE HOLNESS
Firm: 002832 Firm Name: GEORGE HOLNESS
Firm Phone: 347-945-2512  Firm Address: 3870 WHITE PLAINS ROAD BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $115.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEVIN DURANT
Owner Business Name: METRO PCS
Authorized Representative:  KEVIN DURANT
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS DISC SW
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3\0 WIRE
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                   
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 24 + New Meters 1 - Removed Meters 0 = Total Meters 25

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/21/2008 Notice: 1 - FIRST NOTICE 04/13/2009
Power Issued: 04/21/2008 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B303424
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/03/2009 02/09/2009 JMZ N (0) (0) Y
INSPECTION COMMENTS: N
 
(2) 04/08/2009 04/13/2009 JMZ A E (30) (5) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B303424
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE SWITCH NEUTRAL NOT BONDED
OPEN 04/08/2009 04/08/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
DRIVE GROUND RACEWAY NOT CONTINUOUS
OPEN 04/08/2009 04/08/2009
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SERVICE ROOM 20 AMP DISCONNECT SWITCH GROUND NEUTRAL
OPEN 04/08/2009 04/08/2009
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
GARAGE GFI RECEPTACLES
OPEN 04/08/2009 04/08/2009
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO WATER GROUND
OPEN 04/08/2009 04/08/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.