BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B303051
Premises: 21 DODWORTH STREET BROOKLYN BIN: 3073434     Block: 3229   Lot: 35
   
Application Completed and Certified

Filed: 21 DODWORTH ST Census Tract:   393 Health Area:  3200
1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11221 Community Board:   304
DOB Cross Street(s):   BROADWAY,    BUSHWICK AVENUE
Status:   C - JOB IS SIGNED OFF 07/16/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/11/2008 7:55 AM
Application Entered:   04/11/2008 Job Start Date:   04/11/2008
Last Change:   07/16/2008 Job End Date:   04/11/2009
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     06/26/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011990 Licensee Name: DECLAN W DELAHUNTY
Firm: 003662 Firm Name: SHUIR ELEC'L CONTR'S CORP
Firm Phone: 718-414-4840  Firm Address: 4360 BULLARD AVENUE BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $168.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   STORAGE AREA
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM MIRANDA
Owner Business Name: 24 DODWORTH ST. LLC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  ONE 200AMP SERVICE SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  FOUR 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  0NE 3PHASE 42CK PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 12                    
Total Units : 23 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/11/2008 Notice:  06/17/2008
Power Issued: 04/11/2008 Response: V - OBJ WAS REMOVED 06/19/2008

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL1NG 200AMP, 3PH, SERVICE AND INSTALLING OUTLETS AND SWITCHES.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B303051
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/23/2008 04/25/2008 CLC P (45) (0) Y
INSPECTION COMMENTS: CONT NO SHOW UNABLE TO LOCATE WORK
 
(2) 05/05/2008 05/12/2008 CLC A E (30) (2) Y
INSPECTION COMMENTS: N
 
(3) 05/27/2008 06/05/2008 PGR A R E (30) (1) Y
INSPECTION COMMENTS: N
 
(4) 06/13/2008 06/17/2008 PAT H X (45) (0) Y
INSPECTION COMMENTS: N
 
(5) 06/26/2008 06/30/2008 FMO C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B303051
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
1ST FL GARAGE GFCI NOT PROVIDED 511.12
RSLV 05/05/2008 05/05/2008 05/27/2008
 
002 (999) OTHER
1ST FL GARAGE SUPPLEMENTAL ROD CONDUCTOR EXPOSED TO PHYSICAL DAMAGE
RSLV 05/05/2008 05/05/2008 05/27/2008
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
1ST FLOOR OUTLET THROUGHOUT JUMPER WIRE NOT PROVIDED
RSLV 05/27/2008 06/13/2008 06/26/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back