BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B303012
Premises: 20 HIGHLAWN AVENUE BROOKLYN BIN: 3177700     Block: 6668   Lot: 1
   
Application Completed and Certified

Filed: 26 HIGHLAWN AV Census Tract:   404 Health Area:  8522
WHOLE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   T
BROOKLYN, NY 11223 Community Board:   311
Related Job Number:    310012839
DOB Cross Street(s):   WEST 13 STREET,    WEST 12 STREET
Status:   C - JOB IS SIGNED OFF 01/27/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/10/2008 9:52 AM
Application Entered:   04/10/2008 Job Start Date:   04/10/2008
Last Change:   01/27/2009 Job End Date:   06/10/2009
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     12/11/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011539 Licensee Name: ALEXANDER LEVIN
Firm: 003051 Firm Name: A.L. ELECTRICAL CORP.
Firm Phone: 212-206-9141  Firm Address: 307 7TH AVENUE-SUITE 404 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $641.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEXANDER NOVIKOV
Owner Business Name: KRASNITSKY OLEG PARTNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  3PH, 100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3PH, 300AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  4 # 3
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4 # 500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  1PH, 80AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3PH, 100AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 144  490    140  144              
Total Units : 923 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 8 - Removed Meters 0 = Total Meters 8

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/10/2008 Notice: 1 - FIRST NOTICE 11/17/2008
Power Issued: 04/10/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B303012
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/13/2008 11/17/2008 JMZ A E (45) (3) Y
INSPECTION COMMENTS: N
 
(2) 12/11/2008 12/15/2008 JMZ C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B303012
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
SERVICE SWITCH LOAD 500 MCM AND 1/0 NOT APPROVED
RSLV 11/13/2008 11/13/2008 12/11/2008
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
SERVICE SWITCH BOND SMALL
RSLV 11/13/2008 11/13/2008 12/11/2008
 
003 ( 19) DEFECTIVE WIRING IS IN USE
AFCI DEFECTIVE
RSLV 11/13/2008 11/13/2008 12/11/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order