NYC Department of Buildings
Electrical Application Details for App #: B302228
Premises: 408 15 STREET BROOKLYN BIN: 3396049     Block: 1104   Lot: 32
   
Application Completed and Certified

Filed: 406 15 ST Census Tract:   149 Health Area:  4700
CELLAR SUB 1 SUB 2 1-4 FLOORS Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   307
Related Job Number:    301987161
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 01/13/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/19/2008 12:26 PM
Application Entered:   03/19/2008 Job Start Date:   03/20/2008
Last Change:   01/13/2009 Job End Date:   03/20/2009
Appointment Status:   
Last Inspection By:   SELF-CERTIFY       On     01/09/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011395 Licensee Name: GEORGE GRANDVILLE
Firm: 002830 Firm Name: GRAND ELECTRIC , INC.
Firm Phone: 718-326-6000  Firm Address: 3435 FULTON STREET BROOKLYN NY 11208 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $3,132.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup:
Owner Business Name: ARMORY PLAZA INC.
Authorized Representative:  LORENZO LOCICERO
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  2  800 AMP SWITCH
E. Over 1200 AMPS  1  1600 AMP SWITCH
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  7  SETS 0F 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  27  30 CKT PANELS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  3  42CKT PANELS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 465  900    200  465                
Total Units : 2030 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 27 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/19/2008 Notice: 1 - FIRST NOTICE 12/24/2008
Power Issued: 03/19/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADVISORY BOARD 3000 AMP SERVICE DRAWINGS TO FOLLOW

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B302228
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2008 12/24/2008 RPL A E (330) (6)
INSPECTION COMMENTS: SEE VIOLATIONS
 
(2) 01/09/2009 01/12/2009 XXX C R (45) (0)
INSPECTION COMMENTS: ALL VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B302228
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
LOBBY - FIXTURE.MISSING / PIGTAIL
RSLV 12/19/2008 12/19/2008 01/09/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT - SUPPLEMENT GR. TO BUILDING STEEL (BOLT TO SMALL)
RSLV 12/19/2008 12/19/2008 01/09/2009
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
APT. - PANELS (NO DIRECTORY)
RSLV 12/19/2008 12/19/2008 01/09/2009
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BAL. - BUBBLE COVER NOT USED ON BALCONEY
RSLV 12/19/2008 12/19/2008 01/09/2009
 
005 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
MOTOR ROOM ROOF - BOX CABLES NOT IN PANEL
RSLV 12/19/2008 12/19/2008 01/09/2009
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NEUTRAL NOT BONDED TO ENCLOSURE
RSLV 12/19/2008 12/19/2008 01/09/2009