BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B301647
Premises: 339 A 2 STREET BROOKLYN BIN: 3020783     Block: 969   Lot: 47
   
Application Completed and Certified

Filed: 339A 2 ST Census Tract:   135 Health Area:  4200
1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    4 AVENUE,    5 AVENUE
Status:   C - JOB IS SIGNED OFF 08/08/2008 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/05/2008 5:50 PM
Application Entered:   03/05/2008 Job Start Date:   03/05/2008
Last Change:   08/08/2008 Job End Date:   09/06/2008
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     06/23/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011564 Licensee Name: CLEMENT C CHAMBERS
Firm: 003079 Firm Name: K.N.C ELECTRIC INC
Firm Phone: 718-527-7180  Firm Address: 187-27 LINDEN BLVD. ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $165.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GERMAN MONTANA
Authorized Representative:  GERMAN MONTANA
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1 - 200 AMP SER. SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 - 3/0 RISER
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1 - 42 CIRCUIT PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 14  18    15  14              
Total Units : 63 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/05/2008 Notice: 1 - FIRST NOTICE 05/12/2008
Power Issued: 03/05/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B301647
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/08/2008 05/12/2008 PGR A E (50) (5) Y
INSPECTION COMMENTS: N
 
(2) 06/20/2008 06/23/2008 FMO J Y (50) (0) Y
INSPECTION COMMENTS: N
 
(3) 06/23/2008 06/26/2008 HMC C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B301647
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
1ST FLOOR RIM FOR MAN HOLD COVER
RSLV 05/08/2008 05/08/2008 06/20/2008
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
1ST FL SER/GRN NOT RUN TO WATER MAIN
RSLV 05/08/2008 06/20/2008 06/23/2008
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
1ST FLOOR KITCHEN BAR AREA
RSLV 05/08/2008 06/20/2008 06/23/2008
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
1ST FLOOR END LINE BOX LOCKNUT
RSLV 05/08/2008 06/20/2008 06/23/2008
 
005 (999) OTHER
ROOF SER/OUTLET NOT PROVIDED FOR A/C UNIT
RSLV 05/08/2008 06/20/2008 06/23/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.