| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
5 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
120 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
5 |
|
| D. Over 250 MCM |
15 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
120 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
6 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT SER/GRN RACEWAY AT WATER MAIN |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT SER/GRN IN SER/SW NOT ON LINE SIDE |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 003 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED BSMT ALL FEEDER IN 3IN RACEWAY FOR APT |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 004 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION ALL NEED LOAD CALCULATION FOR ENTIRE BUILDING |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF PANEL NEUTRAL BONDED |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 006 |
( 29) |
OUTLET BOXES ARE NOT COVERED ROOF PANEL MISS TRIM |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 007 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX BSMT DIST/B |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 008 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE BSMT DIST/B |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BSMT FIRE PUMP CONTROLLER REMOVED NEUTRAL |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED ALL WIRE TO DRYER OUTLET 10/2 USED |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 011 |
(999) |
OTHER BSMT DOOR NOT AS PER DRAWING SER/ROOM |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |
| |
| 012 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BSMT NEUTRAL BAR USED IN SPLICE BOX IN BSMT FOR APT |
RSLV |
11/10/2008 |
11/10/2008 |
12/30/2008 |