BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B297693
Premises: 1439 PACIFIC STREET BROOKLYN BIN: 3029895     Block: 1203   Lot: 69
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1439 PACIFIC ST Census Tract:   313 Health Area:  2900
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
DOB Cross Street(s):   BROOKLYN AVENUE,    KINGSTON AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   11/09/2007 Job Start Date:   11/10/2007
Last Change:   08/22/2025 Job End Date:   11/30/2007
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     10/04/2011      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011511 Licensee Name: EUSEBIO E MCQUEEN
Firm: 002982 Firm Name: RM ELECTRIC CO., INC.
Firm Phone: 718-272-0065  Firm Address: 240 KENT AVE, SUITE KB/22C BROOKLYN NY 11249 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $79.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM SMITH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/09/2007 Notice: 1 - FIRST NOTICE 10/07/2011
Power Issued: 11/09/2007 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B297693
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2011 10/07/2011 FMO A E (30) (3) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B297693
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
SERVICE ENTRANCE RACEWAY NOT PROPERLY SUPPORTED 350.30
OPEN 10/04/2011 10/04/2011
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
#8 THHN FUSED AT 60 AMPS 240.3
OPEN 10/04/2011 10/04/2011
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
#12 THHN FUSED AT 30 AMPS 240.3
OPEN 10/04/2011 10/04/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.