Electrical Application Details for App #: B295802
Premises: 805 5 AVENUE BROOKLYN BIN: 3010046     Block: 677   Lot: 46
   
Application Completed and Certified

Filed: 805 5 AV Census Tract:   101 Health Area:  4400
209 32ND STREET Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11232 Community Board:   307
Special Place Name:   CAMBRIDGE CON.
Related Job Number:    302215822
DOB Cross Street(s):    4 AVENUE,    5 AVENUE
Status:   C - JOB IS SIGNED OFF 03/25/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2007 4:54 PM
Application Entered:   09/20/2007 Job Start Date:   09/21/2007
Last Change:   03/25/2010 Job End Date:   12/30/2008
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     02/09/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009639 Licensee Name: THOMAS S CARNEY
Firm: 003614 Firm Name: ROYAL ELEC'L & WIRING COR
Firm Phone: 718-584-1424  Firm Address: 2558 MARION AVENUE 1 BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $678.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WILLIAM RUGGIERO
Owner Business Name: JLRB ASSOCIATES, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1) 200 AMP SWITCH
C. 201 Up to 600 AMPS  1  1) 400 AMP SWITCH
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4) 3/0 AWG THHN
D. Over 250 MCM  1  4) 500 MCM AWG
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  12  20 CIRCUIT 1 PHASE 208V
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  30 CIRCUIT 3 PHASE 208V
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 95  320  36  78  95                
Total Units : 624 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 12 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 13 - Removed Meters 0 = Total Meters 13

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/20/2007 Notice: 1 - FIRST NOTICE 12/11/2009
Power Issued: 09/20/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B295802
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/08/2009 09/11/2009 DEX A E (30) (3) Y
INSPECTION COMMENTS: DID NOT INSPECT BUILDING, ONLY SERVICE
 
(2) 12/10/2009 12/11/2009 JMZ V R E (45) (7) Y
INSPECTION COMMENTS: INSPECTED TO 3RD FLOOR
 
(3) 02/09/2010 02/17/2010 JMZ C R (45) (0) Y
INSPECTION COMMENTS: -

OBJECTION FOR APPLICATION #: B295802
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SERVICE SWITCHES NEUTRALS NOT BONDED TO PANEL ENCLOSURES
RSLV 09/08/2009 09/08/2009 12/10/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
MAIN GROUND FOR EQUIPMENT NOT MIN SIZE FOR 500 MCM, NEW (1/0)
RSLV 09/08/2009 09/08/2009 12/10/2009
 
003 ( 19) DEFECTIVE WIRING IS IN USE
NO FUSES FOR 400 AMP SERVICE SWITCHNOT FINAL INSPECTION
RSLV 09/08/2009 09/08/2009 12/10/2009
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
GFI SERVICE ROOM
RSLV 12/10/2009 12/10/2009 02/09/2010
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
SERVICE ROOM PANELS KO'S
RSLV 12/10/2009 12/10/2009 02/09/2010
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BOND ALL RECEPTACLES
RSLV 12/10/2009 12/10/2009 02/09/2010
 
007 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
AFCI GROUND FLOOR SLEEP AREA
RSLV 12/10/2009 12/10/2009 02/09/2010
 
008 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
A/C RECEPTACLE RECREATION ROOM, GROUND FLOOR APT
RSLV 12/10/2009 12/10/2009 02/09/2010
 
009 ( 29) OUTLET BOXES ARE NOT COVERED
PUT ALL COVERS ON
RSLV 12/10/2009 12/10/2009 02/09/2010
 
010 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND RACEWAY NOT COMPLETE
RSLV 12/10/2009 12/10/2009 02/09/2010