| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
1) 200 AMP SWITCH |
| C. 201 Up to 600 AMPS |
1 |
1) 400 AMP SWITCH |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
4) 3/0 AWG THHN |
| D. Over 250 MCM |
1 |
4) 500 MCM AWG |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
12 |
20 CIRCUIT 1 PHASE 208V |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
30 CIRCUIT 3 PHASE 208V |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED SERVICE SWITCHES NEUTRALS NOT BONDED TO PANEL ENCLOSURES |
RSLV |
09/08/2009 |
09/08/2009 |
12/10/2009 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY MAIN GROUND FOR EQUIPMENT NOT MIN SIZE FOR 500 MCM, NEW (1/0) |
RSLV |
09/08/2009 |
09/08/2009 |
12/10/2009 |
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE NO FUSES FOR 400 AMP SERVICE SWITCHNOT FINAL INSPECTION |
RSLV |
09/08/2009 |
09/08/2009 |
12/10/2009 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED GFI SERVICE ROOM |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX SERVICE ROOM PANELS KO'S |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BOND ALL RECEPTACLES |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 007 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED AFCI GROUND FLOOR SLEEP AREA |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 008 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS A/C RECEPTACLE RECREATION ROOM, GROUND FLOOR APT |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 009 |
( 29) |
OUTLET BOXES ARE NOT COVERED PUT ALL COVERS ON |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |
| |
| 010 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY WATER GROUND RACEWAY NOT COMPLETE |
RSLV |
12/10/2009 |
12/10/2009 |
02/09/2010 |