BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B295695
Premises: 175 COLUMBIA HEIGHTS BROOKLYN BIN: 3001740     Block: 234   Lot: 22
   
Application Completed and Certified

Filed: 175 COLUMBIA HEIGHTS Census Tract:   3.01 Health Area:  2300
BSMT & 1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    302364894
DOB Cross Street(s):   CLARK STREET,    PIERREPONT STREET
Status:   C - JOB IS SIGNED OFF 02/19/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/18/2007 4:35 PM
Application Entered:   09/18/2007 Job Start Date:   09/18/2007
Last Change:   02/19/2008 Job End Date:   09/18/2008
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     02/12/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011399 Licensee Name: JEFF SKOWRONSKI
Firm: 002489 Firm Name: INTER CONNECTION ELETRIC
Firm Phone: 718-748-9800  Firm Address: 209 GRANITE AVE STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $113.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAN SOERGEL
Owner Business Name: 175 COLUMBIA HTS HOUSING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#4AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  100A, MLO, 120/208V
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 10  30    10  10              
Total Units : 63 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 1 - Removed Meters 2 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/18/2007 Notice: 1 - FIRST NOTICE 01/28/2008
Power Issued: 09/18/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMBINE APTS AT BSMT FLOOR TO REDUCE OCCUPANCY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B295695
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/22/2008 01/28/2008 CLC V E (30) (2) Y
INSPECTION COMMENTS: N
 
(2) 02/12/2008 02/19/2008 DEX C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B295695
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT 100 AMP SER SW NEUTRAL NOT BONDED 250.28
RSLV 01/22/2008 01/22/2008 02/12/2008
 
002 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
1ST FL BATHROOMS FIXTURES NOT APPROVED FOR WET LOCATION
RSLV 01/22/2008 01/22/2008 02/12/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back