BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B292345
Premises: 68 MASPETH AVENUE BROOKLYN BIN: 3392163     Block: 2907   Lot: 21
   
Application Completed and Certified

Filed: 68 MASPETH AV Census Tract:   477 Health Area:  0900
KINGLANDS AVE Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    301671910
DOB Cross Street(s):   CONSELYEA STREET,    KINGSLAND AVENUE
Status:   C - JOB IS SIGNED OFF 03/11/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/16/2007 6:31 PM
Application Entered:   06/16/2007 Job Start Date:   06/18/2007
Last Change:   03/11/2008 Job End Date:   12/18/2007
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     02/07/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011010 Licensee Name: SALVATORE SIMETI
Firm: 002359 Firm Name: SAL SIMETI ELEC'L CORP.
Firm Phone: 718-418-2345  Firm Address: 59-10 57 STREET MASPETH NY 11378 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $399.50
Other Work:   ADDITIONAL OUTLETS
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SEGAL MAGORY
Owner Business Name: MASPETH AVE LLC
Authorized Representative:   SLKBUILDING@YAHOO.COM
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200AMP SEE B262723
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  3#2 SEE B262723
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  SEE B262723
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   50    30                  
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 0 #10-Wire 0
Existing Meters 10 + New Meters 0 - Removed Meters 0 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/16/2007 Notice: C - CALL TO OFFICE 02/04/2008
Power Issued: 06/16/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BUILDING UNDER NEW OWNER. WE ARE COMPLETING WORK ON APPLICATION B262723, REPAIRS ON ENTIRE BUILDING WIRING TO OUTLETS-SWITCHES-LIGHTING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B292345
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/09/2008 01/11/2008 CLC A E (5) (5)
INSPECTION COMMENTS: N
 
(2) 01/28/2008 02/04/2008 PGR H X (30) (0)
INSPECTION COMMENTS: #18 BATHROOM #19 ALL APT BEDROOM #46 ALL APT
 
(3) 02/07/2008 02/12/2008 CLC C R (15) (0)
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B292345
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ENTIRE APTS KITCHEN COUNTER NO TWO CKTS PROVIDED 210.52
RSLV 01/09/2008 01/28/2008 02/07/2008
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BSMT BATHROOMS BOX CABLES HANGING
RSLV 01/09/2008 01/28/2008 02/07/2008
 
003 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
APT 3B GFCI DEFECTIVE
RSLV 01/09/2008 01/28/2008 02/07/2008
 
004 ( 19) DEFECTIVE WIRING IS IN USE
APT 4B AFCI BREAKER DEFECTIVE
RSLV 01/09/2008 01/28/2008 02/07/2008
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
ENTIRE PANEL NOT LABEL
RSLV 01/09/2008 01/28/2008 02/07/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back