Electrical Application Details for App #: B287796
Premises: 39 CLAVER PLACE BROOKLYN BIN: 3057372     Block: 1997   Lot: 2
   
Application Completed and Certified

Filed: 39 CLAVER PL Census Tract:   227 Health Area:  1300
THE ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   303
Related Job Number:    302193908
DOB Cross Street(s):   JEFFERSON AVENUE,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 07/13/2010 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/08/2007 5:20 PM
Application Entered:   02/08/2007 Job Start Date:   02/12/2007
Last Change:   07/13/2010 Job End Date:   03/01/2007
Appointment Status:   
Last Inspection By:   PETER GREENE       On     05/18/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011068 Licensee Name: CARLOS BERGER
Firm: 003535 Firm Name: BERGER QUALITY ELEC'L CON
Firm Phone: 718-768-3300  Firm Address: 195 7TH AVENUE BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $290.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANOUCK LEFUR
Owner Business Name: OWNER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  3X60AMP 1X100AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  2/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  20-1
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  3  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 46  56  42  47              
Total Units : 201 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 0 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/08/2007 Notice: 1 - FIRST NOTICE 02/01/2010
Power Issued: 02/08/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONVERT TWO FAMILY TO THREE FAMILY RELATED APLICATION # 302193908-01-AL IN THE BUILDINGS DEPARTMENT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B287796
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/26/2010 02/01/2010 FMO A E (45) (6) Y
INSPECTION COMMENTS: N
 
(2) 03/18/2010 03/29/2010 MC2 J Y E (5) (0) Y
INSPECTION COMMENTS: N
 
(3) 05/18/2010 05/20/2010 PGR C R E (25) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B287796
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
OUTLETS THROUGHOUT NOT GROUNDED 250.146
RSLV 01/26/2010 01/26/2010 03/18/2010
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
A OUTLETS ON KITCHEN COUNTER NOT GFCI PROTECTED 210.8
RSLV 01/26/2010 03/18/2010 05/18/2010
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
B NO GFCI PROVIDED IN BOILER ROOM 210.8
RSLV 01/26/2010 03/18/2010 05/18/2010
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
C NO GFCI PROVIDED ON ISLAND 210.8
RSLV 01/26/2010 03/18/2010 05/18/2010
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND BAR USED AS NEUTRAL BAR IN PANELS ON 1ST 2ND FLOOR 350.122
RSLV 01/26/2010 03/18/2010 05/18/2010
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
NO AFCI PROVIDED FOR BEDROOMS 210.12B
RSLV 01/26/2010 03/18/2010 05/18/2010