BIS Menu  |  Applications  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B280897
Premises: 175 7 AVENUE BROOKLYN BIN: 3025169     Block: 1076   Lot: 7
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 175 7 AV Census Tract:   155 Health Area:  4500
NONE Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    1 STREET,    2 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/12/2006 Job Start Date:   07/20/2006
Last Change:   08/22/2025 Job End Date:   10/20/2006
Appointment Status:   
Last Inspection By:   PETER GREENE       On     01/24/2008      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010809 Licensee Name: JOHN L RICKFORD
Firm: 002075 Firm Name: R.J.ELECTRICAL CONTRACTOR
Firm Phone: 718-949-5466  Firm Address: 201-11 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $210.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: WADE HAGENBURT
Owner Business Name: SWEET MELISSA PARK SLOPE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 50  30  10                  
Total Units : 91 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 14 + New Meters 1 - Removed Meters 1 = Total Meters 14

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/12/2006 Notice: 1 - FIRST NOTICE 01/29/2008
Power Issued: 07/12/2006 Response:  

Follow-Up:
Contractor's Comments:  UPGRADE METER SERVICE TO 200 AMPS 4 WIRE 110/208 VOLT AMPREWIRE STORE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B280897
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/24/2008 01/29/2008 PGR V E (50) (5) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B280897
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT - SER/GRN RACEWAY AT 1900 PULL BOX
OPEN 01/24/2008 01/24/2008
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
1ST - PANEL
OPEN 01/24/2008 01/24/2008
 
003 (999) OTHER
1ST FL - PANEL USED AS RACEWAY 312.8
OPEN 01/24/2008 01/24/2008
 
004 (999) OTHER
1ST FL - SERVICE OUTLET NOT PROVIDED FOR A/C UNIT 210.63
OPEN 01/24/2008 01/24/2008
 
005 (999) OTHER
BSMT - ALL CONDUCTORS OF A CIRCUIT NOT IN SAME RACEWAY. FEEDER FROMBSMT TO 1ST FL PNL NEUTRAL 300.3B
OPEN 01/24/2008 01/24/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Property Profile  |  Electrical Inspection Work Order  |  Back