Electrical Application Details for App #: B277236
Premises: 410 WINTHROP STREET BROOKLYN BIN: 3327710     Block: 4829   Lot: 1
   
Application Completed and Certified

Filed: 410 WINTHROP ST Census Tract:   812 Health Area:  4800
1-8 Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   309
Related Job Number:    301916023
DOB Cross Street(s):   NEW YORK AVENUE,    BROOKLYN AVENUE
Status:   C - JOB IS SIGNED OFF 10/21/2008
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/22/2006 Job Start Date:   03/28/2006
Last Change:   10/21/2008 Job End Date:   05/15/2008
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     10/17/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011304 Licensee Name: ANGELO G RIGAS
Firm: 002708 Firm Name: ARC ELEC'L & MECH CONTRS
Firm Phone: 718-222-8162  Firm Address: 26 DELAVAN STREET CORP BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup: ROBERT THELIAN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  33  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  20  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  8  
C. 3 Phase Up to 225 AMPS  33  
D. 3 Phase Over 225 AMPS  48  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  8  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   3000    1500  5000     1750          500 
Total Units : 11750 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/22/2006 Notice: 1 - FIRST NOTICE 08/29/2008
Power Issued: 03/22/2006 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  KINGS COUNTY HOSPITAL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B277236
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/27/2008 08/29/2008 PGR V E (180) (10) Y
INSPECTION COMMENTS: NOT A FINAL INSPECTION - REINSPECT
 
(2) 10/17/2008 10/20/2008 DEX C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B277236
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL FLOORS - ALL GROUND RACEWAY THROUGHOUT
RSLV 08/27/2008 08/27/2008 10/17/2008
 
002 (999) OTHER
BASEMENT - ROOM LAYOUT NOT AS PER DRAWING DOOR
RSLV 08/27/2008 08/27/2008 10/17/2008
 
003 (999) OTHER
ALL - PANIC BAR NOT PROVIDED FOR SERVICE 1200A AND OVER 110.26
RSLV 08/27/2008 08/27/2008 10/17/2008
 
004 (999) OTHER
BASEMENT - FIRE PUMP FUSE NOT AS PER DRAWING
RSLV 08/27/2008 08/27/2008 10/17/2008
 
005 (999) OTHER
BASEMENT - FIRE PUMP SERVICE LINE AND LOAD IN SAME RACEWAY
RSLV 08/27/2008 08/27/2008 10/17/2008
 
006 (999) OTHER
BASEMENT - ALL 30 A FUSE SERVICW SWITCH IN LINE WITH TRANSFORMER NOT AS PER DRAWING 15KVA
RSLV 08/27/2008 08/27/2008 10/17/2008
 
007 (999) OTHER
BASEMENT - SWITCH BOARD SSB2 NOT ON DRAWING
RSLV 08/27/2008 08/27/2008 10/17/2008
 
008 (999) OTHER
7TH FLOOR - ELECTRIC CLOSET PULL BOX CLEARANCE NOT PROVIDED
RSLV 08/27/2008 08/27/2008 10/17/2008
 
009 (999) OTHER
ALL FLOORS CABLE NOT SUPPORTED 7TH FLOOR AND OTHER FLOORS ELECTRICCLOCK
RSLV 08/27/2008 08/27/2008 10/17/2008
 
010 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
ENTIRE - ONE LINE OF ALL PANEL AND FEEDER
RSLV 08/27/2008 08/27/2008 10/17/2008