NYC Department of Buildings
Electrical Application Details for App #: B276805
Premises: 53 BRIDGE STREET BROOKLYN BIN: 3335871     Block: 42   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 53 BRIDGE ST Census Tract:   21 Health Area:  1000
ELEVATORS Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   WATER STREET,    FRONT STREET
Status:   C - JOB IS SIGNED OFF 09/08/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/13/2006 12:35 PM
Application Entered:   03/13/2006 Job Start Date:   03/13/2006
Last Change:   09/08/2020 Job End Date:   02/28/2007
Appointment Status:   
Last Inspection By:   PETER GREENE       On     08/21/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011101 Licensee Name: JOSHUA GUTTMAN
Firm: 001557 Firm Name: ZEV ELECTRIC CORP.
Firm Phone: 718-522-1267  Firm Address: 202 PLYMOUTH STREET 1ST FLR BROOKLYN NY 11201 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010075 FISHBAUM, LEONARD 001557 ZEV ELECTRIC CORP. RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 53 BRIDGE LLC
Authorized Representative:  JACOB SALAMON
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/10/2020
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B276805
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/16/2020 06/16/2020 JGX V (24) (1)
INSPECTION COMMENTS: INCOMPLETE INSPECTION. PASSENGER ELEV #2, ID # 3P11983 ONLY INSPECTED. CONTACT - EPHRAIM HERSKOVITS (347)219-3109. ELEV #1 NOT INSPECTED. 1 OBJECTION ISSUED.
 
(2) 07/17/2020 07/17/2020 OSZ V R (35) (12)
INSPECTION COMMENTS: ELEVATOR CONTRACTOR HAS CONFIRMS THAT ALL ELEVATOR RELATED EQUIPMENT INSTALLED IN 2017 WAS RELOCATED FROM ROOF TO 8TH FLOOR-OBJECTIONS ARE FOR ELEVATOR# 1(ELE# 3P11984). INSPECTION WAS NOT COMPLETED. PIT, MAIN OCPD FOR DISCO AND ALL RELATED CKT'S WERE NOT INSPECTED.
 
(3) 08/10/2020 08/10/2020 DJG V R (20) (3)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE FOR BOTH ELEVATORS 3P11983 AND 3P11984. ALSO SEE APP #B00375717. 3 OBJECTIONS REMAIN, CONTRACTOR TO SELF CERTIFY.
 
(4) 08/21/2020 08/21/2020 PGR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000018156
 
(5) 08/21/2020 08/21/2020 PGR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000018158
 
(6) 08/21/2020 08/21/2020 PGR C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-20-000018162

OBJECTION FOR APPLICATION #: B276805
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(ROOF) DEFECTIVE GFCI AT ROOF OF CAR. AMEND 110.2.A
RSLV 06/16/2020 06/16/2020 07/17/2020
 
002 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 008)FEEDER CONDUCTORS EGC'S IN TROFF UNDER DISCONNECTS HAVE NOT BEENBONDED TO ENCLOSURE. ART. 250.148(C)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008)ARC FLASH LABELING IS REQUIRED FOR EQUIPMENT. ART. 110.16
RSLV 07/17/2020 07/17/2020 08/10/2020
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 008)PENETRATING HOLES FOR FEEDER CONDUCTORS HAVE NOT BEEN FIRE BLOCKED.ART. 300.21
RSLV 07/17/2020 07/17/2020 08/10/2020
 
005 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 008)FEEDER CONDUCTORS UNDER TROFF ARE NOT SUPPORTED. ART. 320.30()
RSLV 07/17/2020 07/17/2020 08/10/2020
 
006 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
(FLOOR: 008)GROUPING OF CKT'S FROM EMT CONDUIT TO PANEL HAS NOT BEEN PROVIDED.ART. 210.4(D)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
007 (247) SIMULTANEOUS OPENING OF POLES
(FLOOR: 008)HANDLE TIES OR 2-POLE OCPD'S ARE REQUIRED FOR CKT'S WITH SHAREDNEUTRALS. ART. 210.4(B)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
008 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 008)KO SEAL IS REQUIRED ON LIFT SIDE OF MOTOR SPLICE BOX. ART. 110.12(A)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
009 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 008) 2-3IN KO'S IN TROFF. ART. 110.12(A)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
010 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 008) MULTIPLE KO'S IN PANEL. ART. 110.12(A)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
011 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 008) MULTIPLE KO'S IN LIGHTING DISCO. ART. 110.12(A)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
012 ( 42) BUSHINGS ARE MISSING OR LOOSE
(FLOOR: 008)PLASTIC BUSHING FOR FEEDER CONDUCTORS IN TROFF UNDER DISCONNECTSWITCHES HAS NOT BEEN PROVIDED. ART. 300.4(G)
RSLV 07/17/2020 07/17/2020 08/10/2020
 
013 (999) OTHER
(FLOOR: 008)CONTRACTOR MUST AMEND APP FOR 2-SET OF #2 AWG FEEDERS CONDUCTORS,DISCO'S, 1-CKT BREAKER PANEL(ELEVATOR ROOM) AND DEVICES IN ELEVATORROOM.
RSLV 07/17/2020 07/17/2020 08/10/2020
 
014 (247) SIMULTANEOUS OPENING OF POLES
(FLOOR: 008)ART. 210.4(A) HANDLE TIES FOR SHARED NEUTRALS NOT PROVIDED IN PANEL.
RSLV 08/10/2020 08/10/2020 08/21/2020
 
015 (999) OTHER
(FLOOR: 008)ART. 110.16. ARCH FLASH LABELS NOT PROVIDED ON DISCONNECTS ANDPANEL.
RSLV 08/10/2020 08/10/2020 08/21/2020
 
016 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(CELLAR) ART. 110.2. DEFECTIVE GFCI IN PIT OF ELEVATOR 3P11984.
RSLV 08/10/2020 08/10/2020 08/21/2020