| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
250.00 |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
06/16/2020 |
06/16/2020 |
JGX |
V |
|
|
(24) |
|
(1) |
|
| INSPECTION COMMENTS:
|
INCOMPLETE INSPECTION. PASSENGER ELEV #2, ID # 3P11983 ONLY INSPECTED. CONTACT - EPHRAIM HERSKOVITS (347)219-3109. ELEV #1 NOT INSPECTED. 1 OBJECTION ISSUED.
|
| |
| (2) |
07/17/2020 |
07/17/2020 |
OSZ |
V |
R |
|
(35) |
|
(12) |
|
| INSPECTION COMMENTS:
|
ELEVATOR CONTRACTOR HAS CONFIRMS THAT ALL ELEVATOR RELATED EQUIPMENT INSTALLED IN 2017 WAS RELOCATED FROM ROOF TO 8TH FLOOR-OBJECTIONS ARE FOR ELEVATOR# 1(ELE# 3P11984). INSPECTION WAS NOT COMPLETED. PIT, MAIN OCPD FOR DISCO AND ALL RELATED CKT'S WERE NOT INSPECTED.
|
| |
| (3) |
08/10/2020 |
08/10/2020 |
DJG |
V |
R |
|
(20) |
|
(3) |
|
| INSPECTION COMMENTS:
|
FAIL. INSPECTION COMPLETE FOR BOTH ELEVATORS 3P11983 AND 3P11984. ALSO SEE APP #B00375717. 3 OBJECTIONS REMAIN, CONTRACTOR TO SELF CERTIFY.
|
| |
| (4) |
08/21/2020 |
08/21/2020 |
PGR |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-20-000018156
|
| |
| (5) |
08/21/2020 |
08/21/2020 |
PGR |
J |
Y |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-20-000018158
|
| |
| (6) |
08/21/2020 |
08/21/2020 |
PGR |
C |
R |
|
(0) |
|
(0) |
|
| INSPECTION COMMENTS:
|
CERTIFIED - OBJ-20-000018162
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (ROOF) DEFECTIVE GFCI AT ROOF OF CAR. AMEND 110.2.A |
RSLV |
06/16/2020 |
06/16/2020 |
07/17/2020 |
| |
| 002 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (FLOOR: 008)FEEDER CONDUCTORS EGC'S IN TROFF UNDER DISCONNECTS HAVE NOT BEENBONDED TO ENCLOSURE. ART. 250.148(C) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008)ARC FLASH LABELING IS REQUIRED FOR EQUIPMENT. ART. 110.16 |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008)PENETRATING HOLES FOR FEEDER CONDUCTORS HAVE NOT BEEN FIRE BLOCKED.ART. 300.21 |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 005 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (FLOOR: 008)FEEDER CONDUCTORS UNDER TROFF ARE NOT SUPPORTED. ART. 320.30() |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 006 |
(243) |
CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED (FLOOR: 008)GROUPING OF CKT'S FROM EMT CONDUIT TO PANEL HAS NOT BEEN PROVIDED.ART. 210.4(D) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 007 |
(247) |
SIMULTANEOUS OPENING OF POLES (FLOOR: 008)HANDLE TIES OR 2-POLE OCPD'S ARE REQUIRED FOR CKT'S WITH SHAREDNEUTRALS. ART. 210.4(B) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 008 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (FLOOR: 008)KO SEAL IS REQUIRED ON LIFT SIDE OF MOTOR SPLICE BOX. ART. 110.12(A) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 009 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (FLOOR: 008) 2-3IN KO'S IN TROFF. ART. 110.12(A) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 010 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 008) MULTIPLE KO'S IN PANEL. ART. 110.12(A) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 011 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 008) MULTIPLE KO'S IN LIGHTING DISCO. ART. 110.12(A) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 012 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (FLOOR: 008)PLASTIC BUSHING FOR FEEDER CONDUCTORS IN TROFF UNDER DISCONNECTSWITCHES HAS NOT BEEN PROVIDED. ART. 300.4(G) |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 013 |
(999) |
OTHER (FLOOR: 008)CONTRACTOR MUST AMEND APP FOR 2-SET OF #2 AWG FEEDERS CONDUCTORS,DISCO'S, 1-CKT BREAKER PANEL(ELEVATOR ROOM) AND DEVICES IN ELEVATORROOM. |
RSLV |
07/17/2020 |
07/17/2020 |
08/10/2020 |
| |
| 014 |
(247) |
SIMULTANEOUS OPENING OF POLES (FLOOR: 008)ART. 210.4(A) HANDLE TIES FOR SHARED NEUTRALS NOT PROVIDED IN PANEL. |
RSLV |
08/10/2020 |
08/10/2020 |
08/21/2020 |
| |
| 015 |
(999) |
OTHER (FLOOR: 008)ART. 110.16. ARCH FLASH LABELS NOT PROVIDED ON DISCONNECTS ANDPANEL. |
RSLV |
08/10/2020 |
08/10/2020 |
08/21/2020 |
| |
| 016 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (CELLAR) ART. 110.2. DEFECTIVE GFCI IN PIT OF ELEVATOR 3P11984. |
RSLV |
08/10/2020 |
08/10/2020 |
08/21/2020 |