Electrical Application Details for App #: B272568
Premises: 77 EASTERN PARKWAY BROOKLYN BIN: 3029622     Block: 1179   Lot: 17
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 77 EASTERN PARKWAY Census Tract:   215 Health Area:  2720
NONE Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   308
DOB Cross Street(s):   UNDERHILL AVENUE,    WASHINGTON AVENUE
Status:   C - JOB IS SIGNED OFF 06/14/2023
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/17/2005 Job Start Date:   10/15/2005
Last Change:   06/14/2023 Job End Date:   12/25/2005
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     06/05/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010462 Licensee Name: ANTONIO CERIELLO
Firm: 002038 Firm Name: ANTONIO CERIELLO ELEC INC
Firm Phone: 718-797-3757  Firm Address: 15 CARROLL STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $63.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MIKE TROISI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 22  10                  
Total Units : 43 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/10/2022
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B272568
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/08/2022 02/08/2022 SGY N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 02/28/2022 02/28/2022 CLX V (30) (6)
INSPECTION COMMENTS: APMT 2E GEN WIRE OBJECTIONS ISSUED ( 2005 INSTALLED = 2002 CODE USED )
 
(3) 03/10/2022 03/10/2022 CLX V X (50) (2)
INSPECTION COMMENTS: INSPECTION COMPLETE APMT 2E OBJECTIONS COULD NOT BE REMOVED AT TIME OF INSPECTION DUE TO ACCELLA ERROR ALL PREVIOUS OBJECTIONS RESOLVED (2 NEW CREATED BY CONTRACTOR ISSUED FOR SELF CERT)
 
(4) 03/21/2022 03/21/2022 EID J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000009133
 
(5) 03/21/2022 03/21/2022 EID J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-22-000009134
 
(6) 06/05/2023 06/05/2023 ECH C R (1) (0)
INSPECTION COMMENTS: PASS, NON-CERTIFIABLE OBJECTIONS REMOVED AS PER PREVIOUS INSPECTORS COMMENTS.

OBJECTION FOR APPLICATION #: B272568
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 002) A/C RECEPTS EGC NOT PROVIDED ART 250.122
RSLV 02/28/2022 02/28/2022 06/05/2023
 
002 (231) NO OTHER OUTLET
(FLOOR: 002) DISH SHARED CIRCUIT WITH COUNTER TOP ART 210.52B2
RSLV 02/28/2022 02/28/2022 06/05/2023
 
003 (247) SIMULTANEOUS OPENING OF POLES
(FLOOR: 002) SILMUTANEOUS OPENING OF POLES IN PANEL ART 2120.4B
RSLV 02/28/2022 02/28/2022 06/05/2023
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 002) OPENINGS IN PANEL KO SEAL & BREAKER BLANKS ART 110.12A
RSLV 02/28/2022 02/28/2022 06/05/2023
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002) GFCI NOT PROVIDED FOR KITCHEN COUNTER TOPS ART 210.8
RSLV 02/28/2022 02/28/2022 06/05/2023
 
006 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 002)THROUGHOUT AFCI NOT PROVIDED FOR REQUIRED RECEPTS ( BEDROOMSRECEPTS ,& A/C RECEPTS ART 210.12B
RSLV 02/28/2022 02/28/2022 06/05/2023
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 002)OLD CLOTH/ FABRIC CONDUCTORS INSTALLED ON 20 AMP OCPS IN PANELART 310.10
RSLV 03/10/2022 03/10/2022 03/21/2022
 
008 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 002) PANEL DIRECTORY NOT COMPLETE/ ACCURATE ART 408.4
RSLV 03/10/2022 03/10/2022 03/21/2022