BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B270746
Premises: 53 FRONT STREET BROOKLYN BIN: 3329418     Block: 36   Lot: 38
   
Application Completed and Certified

Filed: 57 FRONT ST Census Tract:   21 Health Area:  1000
CELLAR Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   YORK STREET,    MAIN STREET
Status:   C - JOB IS SIGNED OFF 01/28/2011
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/16/2005 Job Start Date:   08/20/2005
Last Change:   01/28/2011 Job End Date:   09/20/2005
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     01/28/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009252 Licensee Name: MORRIS HELLER
Firm: 000647 Firm Name: HELLER ELECTRIC CO., INC.
Firm Phone: 718-871-0800  Firm Address: 620 CONEY ISLAND AVE BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $355.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: GAVRIEL RUBAXZKIN
Owner Business Name: GREENDEL DEVELOPERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 38 + New Meters 1 - Removed Meters 0 = Total Meters 39

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/16/2005 Notice: C - CALL TO OFFICE 11/12/2010
Power Issued: 08/16/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CELLAR ADDEMDUM TO APP. B254702

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B270746
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/14/2010 09/20/2010 DEX A E (30) (2) Y
INSPECTION COMMENTS: N
 
(2) 11/08/2010 11/12/2010 FMO H X (5) (0) Y
INSPECTION COMMENTS: N
 
(3) 01/28/2011 01/28/2011 FMO C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B270746
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FIRE PUMP SERVICE SWITCH NOT (600%) OF FULL LOAD CURRENT 695.4(B)
RSLV 09/14/2010 11/08/2010 01/28/2011
 
002 (999) OTHER
CONDUCTORS FOR FIRE PUMP NOT 100.25% OF FULL LOAD CURRENT CONDUCTORS
RSLV 09/14/2010 11/08/2010 01/28/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back