BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B267202
Premises: 374 12 STREET BROOKLYN BIN: 3023268     Block: 1030   Lot: 23
   
Application Completed and Certified

Filed: 374 12 ST Census Tract:   151 Health Area:  4600
NONE Admin Area:   B - BROOKLYN Inspection Area:   F
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    6 AVENUE,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 03/21/2006
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/12/2005 Job Start Date:   05/15/2005
Last Change:   03/21/2006 Job End Date:   06/30/2005
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     03/16/2006      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010284 Licensee Name: GREGORY FEGOS
Firm: 000616 Firm Name: GREGORY FEGOS ELEC., INC.
Firm Phone: 718-353-2010  Firm Address: 31-11 FARRINGTON STREET QUEENS NY 11354 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $127.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: M PAPAVASSILIU
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 40  20    20  40                
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/28/2005
Power Issued: Response: W - OBJ TO BE REMOVED 07/15/2005

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B267202
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/29/2005 07/05/2005 DEX A G (30) (4) Y
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 09/26/2005 10/04/2005 DEX H X (45) (0) Y
INSPECTION COMMENTS: NEED ACCESS TO FIRST FLOOR
 
(3) 12/05/2005 12/14/2005 RJO N (15) (0) Y
INSPECTION COMMENTS: N
 
(4) 12/22/2005 12/28/2005 DEX H X (50) (0) Y
INSPECTION COMMENTS: N
 
(5) 03/16/2006 03/21/2006 DEX C R E (45) (0) Y
INSPECTION COMMENTS: N




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back