BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B262526
Premises: 913 KENT AVENUE BROOKLYN BIN: 3251573     Block: 1912   Lot: 3
   
Application Completed and Certified

Filed: 913 KENT AV Census Tract:   235 Health Area:  1410
DEP WATER TUNNEL #3 Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11205 Community Board:   303
DOB Cross Street(s):   MYRTLE AVENUE,    WILLOUGHBY AVENUE
Status:   C - JOB IS SIGNED OFF 06/03/2013
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/03/2005 Job Start Date:   12/17/2004
Last Change:   06/03/2013 Job End Date:   06/05/2005
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     05/30/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010169 Licensee Name: JOHN RAGAVANIS
Firm: 003027 Firm Name: PJS ELECTRIC, INC.
Firm Phone: 347-306-5511  Firm Address: 2568 EAST 17TH STREET BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $758.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   WATER SHAFT
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: WARREN KURTZ
Owner Business Name: NYC DEPT OF ENVIRONMENTAL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 45  15  10  45     54        45 
Total Units : 222 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/03/2005 Notice: 1 - FIRST NOTICE 04/15/2013
Power Issued: 01/03/2005 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SHAFT 21B

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B262526
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/08/2013 04/15/2013 CJE V E (65) (3) Y
INSPECTION COMMENTS: UNABLE TO INSPECT 3 PANELS
 
(2) 05/30/2013 06/03/2013 DEX C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B262526
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (220) DOUBLE LUGGING IN SERVICE SWITCH
GROUNDING CONDUCTOR NOT CONTINOUS IN 400 SERVICE SWITCH DOUBLEDON ONE LUG 110.14(A)
RSLV 04/08/2013 04/08/2013 05/30/2013
 
002 (220) DOUBLE LUGGING IN SERVICE SWITCH
EQUIPTMENT GROUND CONDUCTOR DOUBLED IN TRANSFORMER 110.14 (A)
RSLV 04/08/2013 04/08/2013 05/30/2013
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
MAIN GROUNDING CONDUCTOR DOUBLED IN TRANSFORMER 110.14 (A)
RSLV 04/08/2013 04/08/2013 05/30/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back