BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B249091
Premises: 9411 SHORE ROAD BROOKLYN BIN: 3155390     Block: 6111   Lot: 1
   
Application Completed and Certified

Filed: 9411 SHORE RD Census Tract:   54 Health Area:  7810
APT# 5H Admin Area:   B - BROOKLYN Inspection Area:   S
BROOKLYN, NY 11209 Community Board:   310
DOB Cross Street(s):    94 STREET,    RIDGE BOULEVARD
Status:   C - JOB IS SIGNED OFF 06/14/2004
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   03/09/2004 Job Start Date:   03/11/2004
Last Change:   06/14/2004 Job End Date:   04/30/2004
Appointment Status:   
Last Inspection By:   O'HARE, R.J.       On     06/02/2004      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011671 Licensee Name: ANGELO ARFANIS
Firm: 003576 Firm Name: FRACCAVENTO ELEC. CORP
Firm Phone: 718-621-9335  Firm Address: 2375 MCDONALD AVE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $73.00
Other Work:   REMOVAL OF VIOLATION
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   COMMERCIAL
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: DEBRA CASALDO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                   
Total Units : 16 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  01/23/2004
Power Issued: Response: F - FILED TO REMOVE OBJECTION 03/09/2004

Follow-Up: X - FILED APPL,NOW CLOSED 03/09/2004
Contractor's Comments:  COMMENT FROM PICKUP DATED 1-16-04 RE;B246352

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B249091
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/16/2004 01/23/2004 RJO W (15) (3)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 06/02/2004 06/14/2004 RJO C R (75) (0) Y
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order