| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE 1ST FL - DEFECTIVE GFCI OUTLET KITCHEN AREA |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 002 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE 3RD FL - DEFECTIVE GFCI OUTLET IN BATHROOM NO GROUND |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 003 |
(290) |
BATHROOM BRANCH CIRCUIT NOT PROVIDED THROUGHOUT - ALL BATHROOMS NEED DEPENDENT CIRCUITS FOR GFCI OUTLETS |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 004 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS 3RD FL- BEDROOM A/C NEEDS DEPENDENT CIRCUITS FOR GFCI OUTLETS |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED OUTSIDE - LIGHTS OUTSIDE NO GROUNDS FOR LIGHTS |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED OUTSIDE LIGHTS OUTSIDE NO GROUNDS |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 007 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED OUTSIDE ROMEX USED OUTSIDE FEEDING LIGHTS NOT APPROVED FOR THEPURPOSE INTENDED |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED THROUGHOUT PUBLIC HALLWAY SENSORS FOR LIGHTS NOT GROUNDED |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |
| |
| 009 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED THROUGHOUT MC CABLES IN PANELS IN APARTMENT NOT BONDED TO PANELENCLOSURE |
RSLV |
06/18/2013 |
06/18/2013 |
12/19/2013 |