BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B148664
Premises: 448 DEAN STREET BROOKLYN BIN: 3018481     Block: 931   Lot: 9
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 448 DEAN ST Census Tract:   129.02 Health Area:  2600
#4586 BSMT Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11217 Community Board:   306
DOB Cross Street(s):    5 AVENUE,    FLATBUSH AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/02/1996 Job Start Date:   07/21/1995
Last Change:   08/22/2025 Job End Date:   01/26/1996
Appointment Status:   
Last Inspection By:   O'HARE, R.J.       On     08/25/1999      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  B - CANCEL POWER AUTH
Objection Disposition:  

License #: 009939 Licensee Name: WARREN GANNES
Firm: 001705 Firm Name: GANECO ELECTRIC CORP.
Firm Phone: 718-882-1638  Firm Address: 1086 E. GUNHILL ROAD BRONX NY 10469 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $104.00
Other Work:   N
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: BIL RU CROP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: K - CANCELLED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/02/1999 Notice: 1 - FIRST NOTICE 09/02/1999
Power Issued: 01/02/1996 Response:  

Follow-Up:
Wires Comments: UPGRADING METERS 40 100AMP 3 WIRE
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B148664
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/12/1996 02/01/1996 BK1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 02/13/1996 02/27/1996 BK1 N (35) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 09/19/1997 12/24/1997 X01 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 04/07/1998 05/08/1998 X01 N (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(5) 08/25/1999 09/02/1999 RJO A B (30) (4)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back