BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B137533
Premises: 9714 3 AVENUE BROOKLYN BIN: 3155816     Block: 6125   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 185 MARINE AV Census Tract:   56.01 Health Area:  7810
N/A APT 4D Admin Area:   B - BROOKLYN Inspection Area:   S
BROOKLYN, NY 11209 Community Board:   310
DOB Cross Street(s):    97 STREET,    98 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/28/1995 Job Start Date:   02/23/1995
Last Change:   08/22/2025 Job End Date:   02/26/1995
Appointment Status:   
Last Inspection By:   ALTON ROSE       On     01/20/1999      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  

License #: 009240 Licensee Name: PATSY RIZZO
Firm: 001120 Firm Name: PATSY RIZZO
Firm Phone: 718-949-1515  Firm Address: 108-15 JAMAICA AVE. QUEENS NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $13.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: MARK CHILEWITZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                 
Total Units : 22 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   N/A Contact Phone:   718 833-5191

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B137533
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/27/1995 03/31/1995 LEN N (20) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 01/20/1999 01/28/1999 RA1 N (20) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 04/14/2000 04/21/2000 RJO Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order