BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B049254
Premises: 387 CLINTON STREET BROOKLYN BIN: 3004351     Block: 339   Lot: 4
   
Application Completed and Certified

Filed: 387 CLINTON ST Census Tract:   67 Health Area:  4000
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
DOB Cross Street(s):   SACKETT STREET,    UNION STREET
Status:   C - JOB IS SIGNED OFF 10/05/1989
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   02/23/1989 Job Start Date:   02/21/1989
Last Change:   09/28/1989 Job End Date:   02/25/1989
Appointment Status:   
Last Inspection By:   KAGAN, B.       On     09/08/1989      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 009514 Licensee Name: RONALD TESTA
Firm: 001416 Firm Name: TESTA ELECTRIC CO., INC
Firm Phone: 718-331-2747  Firm Address: 1435 65TH STREET, 2ND FL BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $37.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: CORRADO INFANTINO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 15  20  10  15                
Total Units : 62 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Wires Comments: FINISH GROUND FLOOR
Contractor's Comments:  BETWEEN SACKET STREET & UNION STREEET

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B049254
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/29/1989 04/04/1989 JMC J G (35) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 07/21/1989 08/07/1989 JMC Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(3) 09/08/1989 09/28/1989 BK1 C G (30) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order