BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A368805
Premises: 71-12 MAIN STREET QUEENS BIN: 4143347     Block: 6619   Lot: 132
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 71-12 MAIN ST Census Tract:   779.02 Health Area:  2011
MAIN STREEET Admin Area:   A - QUEENS Inspection Area:   E
QUEENS, NY 11367 Community Board:   408
Related Job Number:    421196921
DOB Cross Street(s):    71 AVENUE,    71 ROAD
Status:   C - JOB IS SIGNED OFF 12/13/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/30/2017 1:33 PM
Application Entered:   10/30/2017 Job Start Date:   10/30/2017
Last Change:   12/13/2018 Job End Date:   03/15/2018
Appointment Status:   
Last Inspection By:   BASDEO, C       On     12/12/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012077 Licensee Name: STEVEN L BOODHOO
Firm: 003766 Firm Name: K.A.B. ELECTRIC CORP
Firm Phone: 718-454-5464  Firm Address: 212-27 JAMAICA AVENUE QUEENS VILLAGE NY 11428 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,259.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   MIXED USE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BORIS YAKUBOV
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1- 800 AMP 3 PHASE SWITCH
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  FOUR SETS #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  TWO SETS OF 3/0
D. Over 250 MCM  4  FOUR SETS OF 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  FOUR SINGLE AMP PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  TWO 200 AMP PANELS
D. 3 Phase Over 225 AMPS  2  TWO 400 AMP PANELS
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  ONE ELEVATOR
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    35  22    18  35         
001    30  22    16  30         
002    35  22    18  35         
003    35  22    18  35         
Buildings Total 135  88    70  135     18           
Total Units : 446 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/30/2017 Notice: 1 - FIRST NOTICE 11/13/2018
Power Issued: 10/30/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A368805
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/13/2018 11/13/2018 COB V (70) (5)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 12/12/2018 12/12/2018 COB C R (57) (0)
INSPECTION COMMENTS: INSPECTION OK, VIOLATIONS NOT SHOWN ARE REMOVED

OBJECTION FOR APPLICATION #: A368805
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)ALL FLOOR SWITCHES, MC CABLE EQUIPMENT GROUNDING CONDUCTOR NOTBONDED TO ENCLOSURE
RSLV 11/13/2018 11/13/2018 12/12/2018
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)FIRE ALARM FUSE CUT OUT, LINE SIDE NOT BONDED IN DISCONNECT ANDPANEL WHERE TAPPED
RSLV 11/13/2018 11/13/2018 12/12/2018
 
003 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(BASEMENT)SUB PANELS, EACH FED BY 600 MCM NOT PROPERLY PROTECTED, NEED 400AMAIN BREAKER IN EACH PANEL
RSLV 11/13/2018 11/13/2018 12/12/2018
 
004 (999) OTHER
(BASEMENT)SERVICE OVERCURRENT PROTECTION ABOVE 601 A , NOT CORDINATED WITHNEXT DOWNSTREAM OVER CURRENT PROTECTION
RSLV 11/13/2018 11/13/2018 12/12/2018
 
005 (999) OTHER
(BASEMENT)3/0 SERVICE ENTRANCE CONDUCTOR IN HOLLOW SPACE OF BUILDING
RSLV 11/13/2018 11/13/2018 12/12/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order