BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A366773
Premises: 41-42 ELBERTSON STREET QUEENS BIN: 4038862     Block: 1554   Lot: 23
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41-42 ELBERTSON ST Census Tract:   469 Health Area:  1420
APT 100 Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11373 Community Board:   404
DOB Cross Street(s):   ELMHURST AVENUE,    WHITNEY AVENUE
Status:   C - JOB IS SIGNED OFF 02/12/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/11/2017 4:00 PM
Application Entered:   09/11/2017 Job Start Date:   09/11/2017
Last Change:   02/12/2019 Job End Date:   09/11/2018
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     02/12/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012290 Licensee Name: GREGG MARGOLIN
Firm: 003031 Firm Name: GSA ELECTRIC CORP.
Firm Phone: 718-922-3300  Firm Address: 9302 DITMAS AVENUE BROOKLYN NY 11236 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $74.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: IFANTIDES CHRISTOS
Owner Business Name: SEVEN HILLS MGMT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 # 6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  100  10             
Buildings Total 10                
Total Units : 28 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/11/2017 Notice: 1 - FIRST NOTICE 01/10/2018
Power Issued: 09/11/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SUPPLY AND INSTALL 1 - METER AND REWIRE APT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A366773
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/10/2018 01/10/2018 ECH V (53) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(2) 09/04/2018 09/04/2018 AGF J Y (38) (0)
INSPECTION COMMENTS: JOB IN PROGRESS .
 
(3) 02/12/2019 02/12/2019 DEX C R (30) (0)
INSPECTION COMMENTS: DISPUTE IS REMOVED

OBJECTION FOR APPLICATION #: A366773
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR)NEW APARTMENT PANEL IS INCORRECTLY PARALLEL TAPPED ON LOAD SIDE OFMAIN SERVICE SWITCH 310.4
RSLV 01/10/2018 01/10/2018 02/12/2019
 
002 (999) OTHER
(GROUND FLOOR)MAIN BREAKER FOR NEW APARTMENT IN ELECTRICAL SERVICE ROOM IS OVER6'7" PER 240.24
RSLV 01/10/2018 01/10/2018 09/04/2018
 
003 (999) OTHER
(GROUND FLOOR)ELECTRICAL SERVICE ROOM NOT TO BE USED FOR STORAGE PER NYC AMENDMENT110.25
RSLV 01/10/2018 01/10/2018 09/04/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order