BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A366330
Premises: 202-20 45 AVENUE QUEENS BIN: 4125216     Block: 5544   Lot: 14
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 202-20 45 AV Census Tract:   1463 Health Area:  2121
CELLAR,1,2,3 FLOOR Admin Area:   A - QUEENS Inspection Area:   E
QUEENS, NY 11361 Community Board:   411
Related Job Number:    421372623
DOB Cross Street(s):    202 STREET,    203 STREET
Status:   C - JOB IS SIGNED OFF 01/08/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/29/2017 11:38 AM
Application Entered:   08/29/2017 Job Start Date:   08/29/2017
Last Change:   01/08/2019 Job End Date:   08/28/2018
Appointment Status:   
Last Inspection By:   KENNETH ROZANSKY       On     01/08/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010804 Licensee Name: SANG CHEUNG
Firm: 002065 Firm Name: AL-LECTRIC ELECT'L CONTRG
Firm Phone: 212-219-3336  Firm Address: 137 CHRYSTIE STREET NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $376.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 1 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTINE CHOE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  2-100AMP2P 1-100AMP3P
B. 101 Up to 200 AMPS  1  1-200 AMP 3 P
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2-NO.2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  1-3/0 1-4/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  1-100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-100 AMP 1-200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    10    10             
001    12  12    12         
002    10  12    12         
003    20  22    10  20         
Buildings Total 52  54    26  54     13           
Total Units : 199 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 2 #10-Wire 0
Existing Meters 4 + New Meters 4 - Removed Meters 4 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/29/2017 Notice: 1 - FIRST NOTICE 12/08/2018
Power Issued: 08/29/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A366330
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/08/2018 12/08/2018 COB V (24) (1)
INSPECTION COMMENTS: OBJECTION ISSUED FOR CLEARANCE OF SERVICE CONDUCTORS
 
(2) 01/08/2019 01/08/2019 KZY C R (18) (0)
INSPECTION COMMENTS: JOB PASS, OBJECTION RESOLVED BY EXTENDING HEIGHT OF WALL TO PREVENT ACCESS TO SERVICE CONDUCTORS FROM STAIRWAY LANDING.

OBJECTION FOR APPLICATION #: A366330
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002)STAIRS LANDING, SERVICE CONDUCTORS LESS THAN THREE FEET CLEARANCE -230.9
RSLV 12/08/2018 12/08/2018 01/08/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back