Electrical Application Details for App #: A365843
Premises: 35-36 30 STREET QUEENS BIN: 4004124     Block: 341   Lot: 39
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 35-36 30TH ST Census Tract:   53 Health Area:  0710
B'SMT, 1ST, 2ND FLS. Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):    35 AVENUE,    36 AVENUE
Status:   C - JOB IS SIGNED OFF 10/19/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/15/2017 8:26 PM
Application Entered:   08/15/2017 Job Start Date:   08/15/2017
Last Change:   10/19/2018 Job End Date:   08/10/2018
Appointment Status:   
Last Inspection By:   SEVERIANO JOHN       On     09/24/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010432 Licensee Name: RONALD F STEWART
Firm: 001266 Firm Name: RONART ELECTRIC CO
Firm Phone: 718-452-3694  Firm Address: 1672 BROADWAY BROOKLYN NY 11207 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $181.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSAN BENJAMIN
Authorized Representative:  C. ALLEN
Relationship To Owner:   P.M.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  3 100 AMP S.S.
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2 SETS 6-3 RISERS
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  3 12-24 CKT BKR PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10  15    10             
001    15  20  10  15             
002    18  24  11  18             
Buildings Total 43  59  25  43                
Total Units : 179 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 3 - Removed Meters 2 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/15/2017 Notice: 1 - FIRST NOTICE 09/20/2018
Power Issued: 08/15/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A365843
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/24/2018 07/24/2018 NRS V (44) (10)
INSPECTION COMMENTS: OBJS. ISSD.
 
(2) 08/21/2018 08/21/2018 NRS V X (41) (3)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED.
 
(3) 09/19/2018 09/20/2018 EVG V R (26) (1)
INSPECTION COMMENTS: JOB FAILED.
 
(4) 09/24/2018 09/24/2018 SVJ C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000014781

OBJECTION FOR APPLICATION #: A365843
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) 1 & 2 FLOOR:MICRO/HOOD RECE NOT SINGLE 422.16(C)
RSLV 07/24/2018 07/24/2018 09/19/2018
 
002 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(ALL FLOORS) BASEM. PANEL, UNDER KITCHEN SINK GFCI BOX
RSLV 07/24/2018 07/24/2018 09/19/2018
 
003 (999) OTHER
(ALL FLOORS)BASEM. & 1FL.: RECEPTACLES IN MULLBERY COVERS NOT MOUNTED WITH 2SCREWS 406.4(C)
RSLV 07/24/2018 07/24/2018 09/19/2018
 
004 (999) OTHER
(ALL FLOORS)1 & 2 FLOOR: PENINSULA RECEPTACLES NOT LOCATED AS PER 210.52
RSLV 07/24/2018 07/24/2018 09/19/2018
 
005 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) IN SERV. DISCS & LINE SIDE TROUGH
RSLV 07/24/2018 07/24/2018 09/19/2018
 
006 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) GEC CONDUIT ZIPTIED TO WATER PIPE IN CLOSET
RSLV 07/24/2018 07/24/2018 09/19/2018
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) IN LEFT HANDSIDE SERVICE DISCONNECT
RSLV 07/24/2018 07/24/2018 09/19/2018
 
008 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) GEC TRIPLE FOLDED UNDER PIPE END BONDING CONNECTORS
RSLV 07/24/2018 07/24/2018 09/19/2018
 
009 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT) ALL RECEPTACLES
RSLV 07/24/2018 07/24/2018 09/19/2018
 
010 (999) OTHER
(BASEMENT)GFCI BOX SETT TOO DEEP IN BOILER ROOM BEHIND FRONT BOILER 314.20
RSLV 07/24/2018 07/24/2018 09/19/2018
 
011 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(BASEMENT) INTERSYSTEM BONDING BAR NOT CONNECTED TO ANYTHING
RSLV 08/21/2018 08/21/2018 09/19/2018
 
012 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) GEC TERMINATION ON GROUND ROD 110.3
RSLV 08/21/2018 08/21/2018 09/19/2018
 
013 (280) MAIN BONDING JUMPER IS DEFECTIVE
(BASEMENT) MBJ SCREWS NOT TIGHT
RSLV 08/21/2018 08/21/2018 09/19/2018
 
014 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)310.15 B, BREAKERS NEED TO BE DE-RATED BECAUSE OF TO MANY CURRENTCARRYING CONDUCTORS IN THE RACEWAY.
RSLV 09/19/2018 09/19/2018 09/24/2018