| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
1-4000A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
12 |
12- 4#500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (GROUND FLOOR)LINE SIDE BOND UNDERSIZED, TO BE 12.5 % FOR DAISY CHAIN BOND |
RSLV |
08/04/2017 |
08/04/2017 |
10/05/2017 |
| |
| 002 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (GROUND FLOOR)SERVICE ROOM, DISTRIBUTION FUSES(2ND FUSES) NOT INSTALLED |
RSLV |
08/04/2017 |
08/04/2017 |
10/05/2017 |
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE (GROUND FLOOR)SERVICE ROOM, FIRE ALARM FUSE CUT , NOT AS PER PRINT, TO BE 60 ARATED ENCLOSURE |
RSLV |
08/04/2017 |
08/04/2017 |
09/20/2017 |
| |
| 004 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE (GROUND FLOOR)1200 A SHAPEWAYS SWITCH TO BE FUSED AT 1000 A, FOR THREE SETS 500MCM |
RSLV |
08/16/2017 |
08/16/2017 |
10/05/2017 |
| |
| 005 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (FLOOR: 001)FIRE ALARG GEC TAP NOT TERMINATED ON NEUTRAL BAR250.24.(A)(4) |
RSLV |
09/20/2017 |
09/20/2017 |
10/05/2017 |