BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A365059
Premises: 30-02 48 AVENUE QUEENS BIN: 4003546     Block: 287   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 30-02 48 AV Census Tract:   199
1ST FL Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):    30 STREET,    30 PLACE
Status:   C - JOB IS SIGNED OFF 10/11/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/26/2017 Job Start Date:   07/26/2017
Last Change:   10/11/2017 Job End Date:   08/02/2017
Appointment Status:   
Last Inspection By:   GLENN BALZARANO       On     10/05/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011514 Licensee Name: JOHN KAMBOURAKIS
Firm: 002985 Firm Name: MAR-KAM ELEC'L CONTR'G IN
Firm Phone: 718-833-7800  Firm Address: 153 32ND STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,315.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   F - Factory
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   51459     Submittal #: 12A0326  
Owner / Occup:
Owner Business Name: 30-02 48TH EQUITIES,LLC
Authorized Representative:  DAVID PLUMBERG
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1-4000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  12  12- 4#500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/26/2017 Notice: 1 - FIRST NOTICE 09/20/2017
Power Issued: 07/26/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WORK ON APP# A306251 E-FILE HAS BEEN REFILED AS ADVISORY BOARD WORK

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A365059
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2017 08/04/2017 COB V (70) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 08/16/2017 08/16/2017 COB V X (40) (1)
INSPECTION COMMENTS: OBJECTIONS IN BIS REMOVED, NEW OBJECTION ADDED
 
(3) 09/20/2017 09/20/2017 NRS V Y (42) (1)
INSPECTION COMMENTS: ADVISORY PRINT IS NEEDED.
 
(4) 10/05/2017 10/05/2017 GBZ C R (40) (0)
INSPECTION COMMENTS: RE INSPECT PASS

OBJECTION FOR APPLICATION #: A365059
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(GROUND FLOOR)LINE SIDE BOND UNDERSIZED, TO BE 12.5 % FOR DAISY CHAIN BOND
RSLV 08/04/2017 08/04/2017 10/05/2017
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(GROUND FLOOR)SERVICE ROOM, DISTRIBUTION FUSES(2ND FUSES) NOT INSTALLED
RSLV 08/04/2017 08/04/2017 10/05/2017
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(GROUND FLOOR)SERVICE ROOM, FIRE ALARM FUSE CUT , NOT AS PER PRINT, TO BE 60 ARATED ENCLOSURE
RSLV 08/04/2017 08/04/2017 09/20/2017
 
004 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(GROUND FLOOR)1200 A SHAPEWAYS SWITCH TO BE FUSED AT 1000 A, FOR THREE SETS 500MCM
RSLV 08/16/2017 08/16/2017 10/05/2017
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(FLOOR: 001)FIRE ALARG GEC TAP NOT TERMINATED ON NEUTRAL BAR250.24.(A)(4)
RSLV 09/20/2017 09/20/2017 10/05/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.