Electrical Application Details for App #: A364935
Premises: 1726 WOODBINE STREET QUEENS BIN: 4082610     Block: 3457   Lot: 25
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1726 WOODBINE ST Census Tract:   549 Health Area:  2200
BSMT/THRUOUT Admin Area:   A - QUEENS Inspection Area:   G
QUEENS, NY 11385 Community Board:   405
DOB Cross Street(s):   CYPRESS AVENUE,    SENECA AVENUE
Status:   C - JOB IS SIGNED OFF 07/14/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/22/2017 3:56 PM
Application Entered:   07/22/2017 Job Start Date:   07/24/2017
Last Change:   07/14/2018 Job End Date:   06/01/2018
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     07/06/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011169 Licensee Name: LAWRENCE WALSH
Firm: 002541 Firm Name: BDS ELECTRIC CORP.
Firm Phone: 718-598-0000  Firm Address: 220-04 HEMPSTEAD AVENUE QUEENS VILLAGE NY 11429 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $372.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID WEISS
Authorized Representative:  DAVID WEISS
Relationship To Owner:   0WNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  7  7 100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  6 SETS 3#6'S
B. Over #2 to 1/0  1  3#1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  6 100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS             
GND  1A&B  12  40  10  10  12             
MEZ  2A&B  12  40  10  10  12             
MZ1  3A&B  12  40  10  10  12             
Buildings Total 41  128  32  35  41                
Total Units : 277 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 5 + New Meters 7 - Removed Meters 5 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/22/2017 Notice: 1 - FIRST NOTICE 06/19/2018
Power Issued: 07/22/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GUT/REENO FOR 6 APTS AND 7 NEW 100 APT METERS AND 6 PANELS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A364935
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/19/2018 06/19/2018 MYT V (60) (6)
INSPECTION COMMENTS: JOB FAILED. ONLY INSPECTED THE BASEMENT AND HALF THE 1ST FLOOR. MORE TIME IS NEEDED TO INSPECT.
 
(2) 07/06/2018 07/06/2018 ECH C R (33) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: A364935
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NEEDS CORRECT BONDING IN PANELS ART 408.40
RSLV 06/19/2018 06/19/2018 07/06/2018
 
002 (181) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(BASEMENT) HOT WATER HEATER NEEDS A DISCONNECT ART 422.11
RSLV 06/19/2018 06/19/2018 07/06/2018
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) PIPE NEEDS TO BE SUPPORTED ART 358.30
RSLV 06/19/2018 06/19/2018 07/06/2018
 
004 (999) OTHER
(BASEMENT) LOAD SIDE WIRES IN DISCONNECT HITTING FUSE BUS ART 110.12
RSLV 06/19/2018 06/19/2018 07/06/2018
 
005 (999) OTHER
(BASEMENT) CABLE NEEDS TO BE STRAPPED ART 332.30
RSLV 06/19/2018 06/19/2018 07/06/2018
 
006 (999) OTHER
(BASEMENT) GRD ROD NEEDS TO BE DEEPER ART 250.53
RSLV 06/19/2018 06/19/2018 07/06/2018