| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400AMPS |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
#4 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
4 |
1 SET 500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
8 |
20-CIRCUIT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) NO DIRECTORY FOR ALL PANELS THROUGHOUT |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 002 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE (BASEMENT) DEFECTIVE SWITCHES FOR LOW VOLTAGE LIGHTS IN HALLWAY |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 003 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (BASEMENT)CABLES AND WIRES HANG SERVICE AREA NOT TERMINATED PROPERLY |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) LAUNDRY ROOM MISSING COVERS |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 005 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (BASEMENT) LAUNDRY ROOM OUTLET NEXT TO SINK NOT GFCI PROTECTED |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 006 |
(999) |
OTHER (BASEMENT) SERVICE ROOM USE AS LAUNDRY ROOM 110.26 |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |
| |
| 007 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ROOF) NO ACCESS FOR COMPRESSORS DISCONNECT |
RSLV |
01/19/2018 |
01/19/2018 |
11/05/2018 |