Electrical Application Details for App #: A364390
Premises: 30-36 14 STREET QUEENS BIN: 4005663     Block: 516   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 30-36 14 ST Census Tract:   79 Health Area:  0300
1ST FL Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
DOB Cross Street(s):    30 ROAD,    30 DRIVE
Status:   C - JOB IS SIGNED OFF 12/17/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/08/2017 3:59 PM
Application Entered:   07/08/2017 Job Start Date:   07/08/2017
Last Change:   12/17/2018 Job End Date:   07/08/2018
Appointment Status:   
Last Inspection By:   JOSEPH RUGGERO       On     12/17/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010527 Licensee Name: VASILIOS MATSIKAS
Firm: 001702 Firm Name: TOWER ELECTRIC INC.
Firm Phone: 718-937-2700  Firm Address: 21-19 40TH AVENUE L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $74.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CONTRACTOR ESTABLISH
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTONIS FAROZES
Owner Business Name: ALPHA GLASS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    26  22    12  26         
Buildings Total 26  22    12  26              
Total Units : 89 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/19/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONTRACTORS ESTABLISHMENT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A364390
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/18/2017 07/18/2017 EVG V (46) (3)
INSPECTION COMMENTS: JOB FAILED.
 
(2) 07/18/2018 07/19/2018 AGF V Y (18) (2)
INSPECTION COMMENTS: FAIL.. OBJECTION STILL EXIST / SEE ALSO NEW OBJECTION
 
(3) 12/17/2018 12/17/2018 JUY C R (35) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: A364390
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF) ROOF AC UNIT IS OVER FUSED AT 30A MAX SHOULD BE 25.
RSLV 07/18/2017 07/18/2017 07/18/2018
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) USED 14 GAUGE TC CABLE FOR WALL MOUNT SPLIT UNITS.
RSLV 07/18/2017 07/18/2017 12/17/2018
 
003 (999) OTHER
(ROOF) SERVICE RECEPTACLE ON THE ROOF NEEDS TO BE WT/TR.
RSLV 07/18/2017 07/18/2017 12/17/2018
 
004 (999) OTHER
(ROOF)DOUBLE LUGGING INUSE IN BOTH A/C CONDENSER DISCONNECTS , ART. 110.14
RSLV 07/18/2018 07/18/2018 12/17/2018
 
005 (999) OTHER
(ROOF) NEUTRALS BONDED INSIDE A/C CONDENSER DISCONNECTS , ART. 250
RSLV 07/18/2018 07/18/2018 12/17/2018