BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A364206
Premises: 17-03 HIMROD STREET QUEENS BIN: 4081875     Block: 3429   Lot: 58
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1703 HIMROD ST Census Tract:   545 Health Area:  1600
THROUGHOUT Admin Area:   A - QUEENS Inspection Area:   G
QUEENS, NY 11385 Community Board:   405
DOB Cross Street(s):   CYPRESS AVENUE,    SENECA AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/02/2017 5:29 PM
Application Entered:   07/02/2017 Job Start Date:   07/05/2017
Last Change:   08/22/2025 Job End Date:   07/05/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MICHAEL BENISCHEK       On     05/11/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 009968 Licensee Name: SIGMOND FRIED
Firm: 000558 Firm Name: FRIED ELECTRIC CO.
Firm Phone: 718-389-2141  Firm Address: 67 WEST STREET, UNIT 321 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $538.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ABE FRIEDMAN
Owner Business Name: NONE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMPS
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20-CIRCUIT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  6  30-CIRCUIT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  PLP  10  10    10             
001  1L  10  25    10         
001  1R  10  25    10         
002  2L  10  25    10         
002  2R  10  25    10         
003  3L  10  25    10         
003  3R  10  25    10         
Buildings Total 70  160    54  70     30           
Total Units : 384 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 7 + New Meters 7 - Removed Meters 7 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/02/2017 Notice: 1 - FIRST NOTICE 05/11/2018
Power Issued: 07/02/2017 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A364206
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/26/2018 02/26/2018 DEX N (10) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 05/11/2018 05/11/2018 MBE V (75) (10)
INSPECTION COMMENTS: OBJECTIONS ISSUED - ALL APT'S APPLICATION SHALL BE AMENDED TO SHOW ALL WORK PERFORMED THERE ARE OVER 25 + FIXTURES, 14 + SWITCH AND OUTLETS.( ALL APT'S NEED RE-INSPECTION ) ONLY BASEMENT & ROOF INSPECTED.

OBJECTION FOR APPLICATION #: A364206
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)APPLICATION ON FILE DOES NOT MATCH ALL WORK PERFORMED IN ALL SIXAPT'S - COUNT ON FIXTURES, SWITCHES, & OUTLETS ARE OVER THE COUNT.
OPEN 05/11/2018 05/11/2018
 
002 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(BASEMENT)NOT PROVIDED WITH CLEARANCE FOR PLP METER AND DISCONNECT (LEFT TORIGHT) ART # 110.26
OPEN 05/11/2018 05/11/2018
 
003 (183) DISCONNECT IS NOT READILY ACCESSIBLE
(BASEMENT)NO CLEARANCE PROVIDED FOR MAIN DISCONNECT DOOR SWING AND SPACE INFRONT NOT PROVIDED (DOOR BUCK IS IN FRONT OF DISCONNECT) ART #620.51
OPEN 05/11/2018 05/11/2018
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)ROMEX CABLE HANGING OUT OF HOLE IN WALL OVER WATER MAIN AND NOT SAFEOFF. AMEND 110.2 (A)
OPEN 05/11/2018 05/11/2018
 
005 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) NOT PROVIDED WATER METER GROUNDING JUMPER. ART # 250.53
OPEN 05/11/2018 05/11/2018
 
006 ( 53) GFCI HAS NOT BEEN PROVIDED
(BASEMENT)HAS NOT BEEN PROVIDED FOR ALL LAUNDRY ROOM OUTLETS, AND BEHINDWASHING MACHINES. ART # 210.8
OPEN 05/11/2018 05/11/2018
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
(ROOF)CONDULETS COVERS ARE NOT PROVIDED WATER CAN ENTER ALL DRAIN PIPEWATER RUN OFF ENTERS ALL FITTINGS AND LB'S ART # 314.25
OPEN 05/11/2018 05/11/2018
 
008 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(ROOF) CONDUIT FITTING ARE LOOSE CHANGE OVER AND ALL REDUCERS.
OPEN 05/11/2018 05/11/2018
 
009 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(ROOF)ALL A/C CONDUITS ARE NOT SUPPORTED AT ALL CONDUITS UNDER ALL UNITS.ART # 342.30
OPEN 05/11/2018 05/11/2018
 
010 (999) OTHER
(ROOF)ALL A/C UNIT CONDUITS AND SEALTIGHT CONDULETS CAN BE CORRODED AND ISNOT SUPPORTED LAYING ON ROOF FLOOR (PHYSICAL DAMAGE CAN BE CAUSED)
OPEN 05/11/2018 05/11/2018