| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
200 AMPS |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
6 |
#3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
20-CIRCUIT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
6 |
30-CIRCUIT |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)APPLICATION ON FILE DOES NOT MATCH ALL WORK PERFORMED IN ALL SIXAPT'S - COUNT ON FIXTURES, SWITCHES, & OUTLETS ARE OVER THE COUNT. |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 002 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (BASEMENT)NOT PROVIDED WITH CLEARANCE FOR PLP METER AND DISCONNECT (LEFT TORIGHT) ART # 110.26 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 003 |
(183) |
DISCONNECT IS NOT READILY ACCESSIBLE (BASEMENT)NO CLEARANCE PROVIDED FOR MAIN DISCONNECT DOOR SWING AND SPACE INFRONT NOT PROVIDED (DOOR BUCK IS IN FRONT OF DISCONNECT) ART #620.51 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 004 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT)ROMEX CABLE HANGING OUT OF HOLE IN WALL OVER WATER MAIN AND NOT SAFEOFF. AMEND 110.2 (A) |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 005 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (BASEMENT) NOT PROVIDED WATER METER GROUNDING JUMPER. ART # 250.53 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (BASEMENT)HAS NOT BEEN PROVIDED FOR ALL LAUNDRY ROOM OUTLETS, AND BEHINDWASHING MACHINES. ART # 210.8 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 007 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ROOF)CONDULETS COVERS ARE NOT PROVIDED WATER CAN ENTER ALL DRAIN PIPEWATER RUN OFF ENTERS ALL FITTINGS AND LB'S ART # 314.25 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 008 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE (ROOF) CONDUIT FITTING ARE LOOSE CHANGE OVER AND ALL REDUCERS. |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 009 |
( 8) |
CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC) (ROOF)ALL A/C CONDUITS ARE NOT SUPPORTED AT ALL CONDUITS UNDER ALL UNITS.ART # 342.30 |
OPEN |
05/11/2018 |
05/11/2018 |
|
| |
| 010 |
(999) |
OTHER (ROOF)ALL A/C UNIT CONDUITS AND SEALTIGHT CONDULETS CAN BE CORRODED AND ISNOT SUPPORTED LAYING ON ROOF FLOOR (PHYSICAL DAMAGE CAN BE CAUSED) |
OPEN |
05/11/2018 |
05/11/2018 |
|