BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A362725
Premises: 22-34 JACKSON AVENUE QUEENS BIN: 4596913     Block: 86   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 22-44 JACKSON AV Census Tract:   19 Health Area:  0720
FIRST FLOOR Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    420651912
DOB Cross Street(s):    46 AVENUE,    23 STREET
Status:   C - JOB IS SIGNED OFF 04/20/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/24/2017 1:57 PM
Application Entered:   05/24/2017 Job Start Date:   07/03/2017
Last Change:   04/20/2022 Job End Date:   07/31/2018
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     04/20/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012629 Licensee Name: ROBERT M MARKS
Firm: 004464 Firm Name: DIFAZIO ELECTRIC NY, INC
Firm Phone: 212-684-5350  Firm Address: 32 EAST 31ST STREET, 8TH FLR NEW YORK NY 10016 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID WALKOFF
Owner Business Name: G&M REALTY, LP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  12  
B. Each Additional 10 Floors Or Less  48  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/08/2021
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELEVATORS: TWELVE(12) (PE1-PE12) NOT RESPONSIBLE FOR MAIN LINE DISCONNECT SW, CAB LIGHTING DISCONNECT SW, FEEDER & BRANCH CIRCUITS TO CONTROLLERS, PIT & MACHINE ROOM LIGHTING, OVERHEAD & SUMP PUMP WIRING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A362725
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/08/2021 12/08/2021 EVG V (139) (3)
INSPECTION COMMENTS: JOB FAILED. INSPECTION COMPLETE.
 
(2) 02/16/2022 02/16/2022 GBZ N (14) (0) Y
INSPECTION COMMENTS: FAIL NO SHOW
 
(3) 04/20/2022 04/20/2022 EVG C R (109) (0)
INSPECTION COMMENTS: JOB PASSED. INSPECTION COMPLETE.

OBJECTION FOR APPLICATION #: A362725
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) ALL MOTORS ARE OVER FUSED. SHOULD BE AT 100 AMPS.
RSLV 12/08/2021 12/08/2021 04/20/2022
 
002 (999) OTHER
(BASEMENT)CONTRACTOR NEEDS TO LOCATE ALL BREAKERS FOR THE PIT LIGHT ANDRECEPTACLES.
RSLV 12/08/2021 12/08/2021 04/20/2022
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ROOF)300.4 G, ALL MOTOR DISCONNECTS NEED BUSHINGS FOR WIRES LARGER THAN#4.
RSLV 12/08/2021 12/08/2021 04/20/2022



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back