BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A362486
Premises: 169-30 BAISLEY BOULEVARD QUEENS BIN: 4542666     Block: 12529   Lot: 230
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 16930 BAISLEY BLVD Census Tract:   334.01 Health Area:  3532
ROOF Admin Area:   A - QUEENS Inspection Area:   K
QUEENS, NY 11434 Community Board:   412
Special Place Name:   AT&T
DOB Cross Street(s):   LIRR ATLANTIC LINE,    MARSDEN STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/18/2017 8:29 PM
Application Entered:   05/18/2017 Job Start Date:   05/18/2017
Last Change:   08/22/2025 Job End Date:   05/15/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     08/23/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011811 Licensee Name: KEVIN GARRITY
Firm: 003666 Firm Name: ALL-STAR ELEC'L SERVICES
Firm Phone: 212-268-7827  Firm Address: 35 WEST 31ST ST. SUITE 703A INC NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $237.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CRAIG CAMPBELL
Owner Business Name: LOCUST MANOR FAMILY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  225 PANEL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
ROF    10      80           
Buildings Total 11                    
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/18/2017 Notice: 1 - FIRST NOTICE 08/23/2017
Power Issued: 05/18/2017 Response:  

Follow-Up:
Contractor's Comments:  NEW AT&T COMMUNICATION SITE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A362486
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/23/2017 08/23/2017 DEX V (50) (2)
INSPECTION COMMENTS: INSTALLED GENERATOR ON ROOF AND DC RECTIFIERS AND AC UNITS. RESOLVE DISPUTES FOR SIGN OFF

OBJECTION FOR APPLICATION #: A362486
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)ADDED 200 AMP SERVICE SWITCH TO EXISTING 1000 KVA SERVICE SYSTEM
OPEN 08/23/2017 08/23/2017
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ROOF)GENERATOR BONDED AFTER SERVICE SWITCH TRANSFER SWITCH ALL NEUTRALSARE GROUPED..
OPEN 08/23/2017 08/23/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order