BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A361011
Premises: 26-33 28 STREET QUEENS BIN: 4617305     Block: 596   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26-33 28 ST Census Tract:   69 Health Area:  0300
ENTIRE BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
Special Place Name:   26-33 28ST LLC
Related Job Number:    421019329
DOB Cross Street(s):   ASTORIA BOULEVARD,    NEWTOWN AVENUE
Status:   C - JOB IS SIGNED OFF 06/18/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/11/2017 12:24 PM
Application Entered:   04/11/2017 Job Start Date:   04/13/2017
Last Change:   06/18/2019 Job End Date:   04/01/2019
Appointment Status:   
Last Inspection By:   JOSEPH RUGGERO       On     05/28/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $715.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RAID M SUKKARIEH
Owner Business Name: 26-33 28ST. LLC
Authorized Representative:  CARLOS ROMERO
Relationship To Owner:   ELECT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  3 PH 400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  8  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  9  8APT,1PL&P.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    20  15    10  20             
001  22  20    11  22         
001  22  20    11  22         
002  22  20    11  22         
002  22  20    11  22         
003  22  20    11  22         
003  22  20    11  22         
004  22  20    11  22         
004  22  20    11  22         
Buildings Total 196  175    98  196              
Total Units : 673 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/11/2017 Notice: 1 - FIRST NOTICE 04/08/2019
Power Issued: 04/11/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  TEMPS MAINTAINED BY OTHER FIRM, ONLY PERM WIRING AND SERVICE AS PER NYC CODE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A361011
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/27/2018 07/27/2018 EVG J (40) (0) Y
INSPECTION COMMENTS: JOB STILL IN PROGRESS. 2ND, 3RD, AND 4TH FLOORS HAVE BEEN INSPECTED AND ONLY NEED TO HAVE ALL THE SMOKE BOXES COVERED. COULD NOT INSPECT THE SERVICE BECAUSE IT WAS COVERED FOR PAINTING. 1ST FLOOR NEEDS TO BE COMPLETED, AC UNITS NOT COMPLETE ON THE ROOF.
 
(2) 04/08/2019 04/08/2019 STP V (40) (7)
INSPECTION COMMENTS: FAIL. DID NOT INSPECT PROPERTY LINE BOX AND TERMINAL BOX AFTER 300 AMP FUSE AND TROUGH.
 
(3) 05/28/2019 05/28/2019 JUY C R (45) (0)
INSPECTION COMMENTS: RESOLVED OBJECTIONS

OBJECTION FOR APPLICATION #: A361011
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR) FIRE ALARM SERVICE NO WORK SPACE 110.26
RSLV 04/08/2019 04/08/2019 05/28/2019
 
002 (999) OTHER
(GROUND FLOOR)FIRE ALARM SERVICE WIRED/GROUNDED/GROUNDING PROPER 250.50
RSLV 04/08/2019 04/08/2019 05/28/2019
 
003 (999) OTHER
(GROUND FLOOR) FIRE ALARM GROUNDING BAR WITH ZIPPIES 250.8
RSLV 04/08/2019 04/08/2019 05/28/2019
 
004 (999) OTHER
(GROUND FLOOR) BATH MEDICINE CABINET NO ACCESS TO BOX 314.29
RSLV 04/08/2019 04/08/2019 05/28/2019
 
005 (999) OTHER
(GROUND FLOOR)TERMINAL BOX OFF 300 AMP FUSE NO ACCESS TO WIRES 314.29
RSLV 04/08/2019 04/08/2019 05/28/2019
 
006 (999) OTHER
(GROUND FLOOR) KITCHEN LED DRIVERS NOT LISTED 110.3
RSLV 04/08/2019 04/08/2019 05/28/2019
 
007 (999) OTHER
(GROUND FLOOR)KITCHEN LED DRIVER CLASS 1 AND CLASS 2 SAME BOX 725.136
RSLV 04/08/2019 04/08/2019 05/28/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order