Premises: 23-26 101 STREET QUEENS BIN: 4040816     Block: 1637   Lot: 18
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2326 101 ST Census Tract:   357 Health Area:  0610
ALL FLOORS Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11369 Community Board:   403
DOB Cross Street(s):    23 AVENUE,    24 AVENUE
Status:   C - JOB IS SIGNED OFF 11/14/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/26/2017 9:05 PM
Application Entered:   03/26/2017 Job Start Date:   03/26/2017
Last Change:   11/14/2017 Job End Date:   03/23/2018
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     07/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012381 Licensee Name: DAVID H GONZALEZ
Firm: 004174 Firm Name: GONCO ELECTRICAL CORP
Firm Phone: 718-418-0011  Firm Address: 1332 HALSEY STREET BROOKLYN NY 11237 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $221.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAIME LOPEZ
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  100 AMP
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  # 2 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  20-1 POLE BREAKER PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    19             
002    24             
Buildings Total 11  52  14  16                
Total Units : 100 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 2 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/26/2017 Notice: 1 - FIRST NOTICE 06/22/2017
Power Issued: 03/26/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RENOVATION REHABILATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A360458
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/07/2017 06/08/2017 COB V (61) (6)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 06/22/2017 06/22/2017 EVG V R (47) (3)
INSPECTION COMMENTS: FAIL
 
(3) 07/12/2017 07/12/2017 EVG C R (41) (0)
INSPECTION COMMENTS: JOB PASSED.

OBJECTION FOR APPLICATION #: A360458
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 002) PANEL, NEUTRALS TERMINATED ON GROUND BAR
RSLV 06/07/2017 06/07/2017 06/22/2017
 
002 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(FLOOR: 002)BATHROOM, FIXTURE NOT LISTED FOR WET LOCATION, INSTALLED IN SHOWERZONE
RSLV 06/07/2017 06/07/2017 06/22/2017
 
003 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)SERVICE PANELS, CONCENTRIC KNOCK OUTS, BONDING BUSHINGS REQUIRED TOBOND ENCLOSURE
RSLV 06/07/2017 06/07/2017 06/22/2017
 
004 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
(BASEMENT) RECREATING SPACE
RSLV 06/07/2017 06/07/2017 06/22/2017
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)WATER MAIN, GROUNDING CONDUCTOR SPLICED, STRANDED AT WATER MAIN ANDSOLID AT DETAIL BAR
RSLV 06/07/2017 06/07/2017 06/22/2017
 
006 (999) OTHER
(OPEN SPACE) GFCI RECEPTACLES, WR RECEPTACLES NOT PROVIDED
RSLV 06/07/2017 06/07/2017 06/22/2017
 
007 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) LOCK NUTS ARE NOT MADE UP TIGHT ON THE SERVICE EQUIPMENT.
RSLV 06/22/2017 06/22/2017 07/12/2017
 
008 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)WIRES ARE NOT COMPLETELY IN THE CONNECTORS ON THE FEEDER CABLES.
RSLV 06/22/2017 06/22/2017 07/12/2017
 
009 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)GROUNDING CONDUCTOR IS NOT CONTINUOUS COMING FROM WATER MAIN.
RSLV 06/22/2017 06/22/2017 07/12/2017