BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A358667
Premises: 109-51 164 STREET QUEENS BIN: 4216721     Block: 10182   Lot: 41
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 109-51 164 ST Census Tract:   258 Health Area:  3400
BASEMENT Admin Area:   A - QUEENS Inspection Area:   J
QUEENS, NY 11433 Community Board:   412
Related Job Number:    421250185
DOB Cross Street(s):    109 AVENUE,    110 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/06/2017 5:48 PM
Application Entered:   02/06/2017 Job Start Date:   02/06/2017
Last Change:   08/22/2025 Job End Date:   02/06/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOSEPH RUGGERO       On     03/15/2024      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012324 Licensee Name: GERBERT BONHOMME
Firm: 004105 Firm Name: SUPREME ELECTRIC CORP
Firm Phone: 718-658-1078  Firm Address: 107-54 SUTPHIN BLVD JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $100.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BAKSH FAIZUL
Owner Business Name: N/A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#2 CONDUCTOR
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  20/20 W/ 100 MAIN
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 3 - Removed Meters 2 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 02/06/2017 Notice: 1 - FIRST NOTICE 03/15/2024
Power Issued: 02/06/2017 Response:  

Follow-Up:
Contractor's Comments:  NEW SERVICE IN ORDER TO LEGALIZED 2 FAMILY DWELLING. OVER HEAD SERVICE 3 METERS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A358667
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/15/2024 03/15/2024 JUY V (1) (2)
INSPECTION COMMENTS: INSP. INCOMPLETE. FULL RE-INSPECTION REQUIRED, WAS AT THE PROPERTY FOR SOLAR INSPECTION ONLY, SEE OBJECTIONS.

OBJECTION FOR APPLICATION #: A358667
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (104) SERVICE CONDUCTORS IN HOLLOW SPACE OF FRAME BUILDING
(BASEMENT) SERVICE ENTRANCE CONDUIT HOLLOW IN FRAME ADM 230.43
OPEN 03/15/2024 03/15/2024
 
002 (329) OPENINGS TO BE SEALED
(OPEN SPACE)METER SOCKET OUTSIDE NOT COVERED OR NOT ENCLOSED WITH APPROVE COVER230.62B
OPEN 03/15/2024 03/15/2024



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order