| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
8 |
100A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 A 3 PHASE |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
3X2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
4X500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
7 |
24 BREAKERS PANELS |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (BASEMENT) GEC FROM WATER MAIN SPLICED |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 002 |
(999) |
OTHER (BASEMENT) GEC RACEWAY FROM WATER NOT CONTINUOUS ART 250.68E |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 003 |
(999) |
OTHER (BASEMENT) WATER GROUND CLAMP CORRODED ART 110.12B |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 004 |
(999) |
OTHER (BASEMENT) 1RR,1R,1F SERVICE SWITCHES NO WATER GROUND ART 250.24A1 |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 005 |
(999) |
OTHER (BASEMENT) 1RR,1R,1F, NO SUPPLEMENTAL GROUND ART 250.53 |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 006 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (GROUND FLOOR) 1R 1RR NO 3' CLEARANCE FOR PANELS |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 007 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (GROUND FLOOR) 1R PANEL NEUTRAL BONDED |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |
| |
| 008 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (GROUND FLOOR) 1R 1RR NO PANEL SCHEDULES |
RSLV |
02/07/2017 |
02/07/2017 |
04/03/2017 |