Electrical Application Details for App #: A356404
Premises: 30-02 48 AVENUE QUEENS BIN: 4003546     Block: 287   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 30-02 48TH AV Census Tract:   199 Health Area:  0800
ELEVATOR MACHINE ROOM AND PIT Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):    30 STREET,    30 PLACE
Status:   C - JOB IS SIGNED OFF 10/07/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/30/2016 10:55 AM
Application Entered:   11/30/2016 Job Start Date:   11/30/2016
Last Change:   10/07/2019 Job End Date:   11/30/2017
Appointment Status:   
Last Inspection By:   BASDEO, C       On     10/02/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012128 Licensee Name: JOHN DICAPUA
Firm: 003833 Firm Name: CAPUTEK ELEC'L SERVICES,
Firm Phone: 718-610-9299  Firm Address: 1460 BROADWAY, 7TH FLOOR INC NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   L2-LOFT BUILDING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BRICKMAN 48TH AVE LIC,LLC
Authorized Representative:  DOUG BARNES
Relationship To Owner:   MANAGING AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  EXISTING 4F163, NEW TBD
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/24/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONVERTING FREIGHT ELEVATOR TO A PASSENGER ELEVATOR 4F163/4P____. WORK IS LIMITED TO POWER AND LIGHT IN ELEVATOR PIT AND MACHINE ROOM ONLY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A356404
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/24/2019 09/24/2019 EVG V (42) (3)
INSPECTION COMMENTS: JOB FAILED.
 
(2) 10/02/2019 10/02/2019 COB C R (61) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A356404
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR)PIT RECEPTACLE AND PUMP CIRCUIT FOR THE ELEVATOR MUST BE LOCATED.
RSLV 09/24/2019 09/24/2019 10/02/2019
 
002 ( 13) THE CONDUCTORS FEEDING THE MOTORS ARE NOT OF PROPER SIZE
(ROOF)FEEDER WIRES FOR THE MOTOR ARE TO SMALL, BASED ON THE OUTPUT OF THEMOTOR PLUS THE ALLOWED INCREASE FOR THE MOTOR.
RSLV 09/24/2019 09/24/2019 10/02/2019
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF)430.42, FUSES ARE TO SMALL ACCORDING TO PROTECTIVE DEVICE RATINGSFOR MOTORS.
RSLV 09/24/2019 09/24/2019 10/02/2019