BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A355418
Premises: 118-15 150 AVENUE QUEENS BIN: 4256899     Block: 11819   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 118-15 150 AV Census Tract:   846.01 Health Area:  3611
BAS,1ST, 2ND PLOOR,GARAGE,POOL Admin Area:   A - QUEENS Inspection Area:   L
QUEENS, NY 11420 Community Board:   410
DOB Cross Street(s):    118 STREET,    LEFFERTS BOULEVARD
Status:   C - JOB IS SIGNED OFF 10/06/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/01/2016 1:49 PM
Application Entered:   11/01/2016 Job Start Date:   11/04/2016
Last Change:   10/06/2017 Job End Date:   12/04/2016
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     10/03/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010159 Licensee Name: FRANK J FODERA
Firm: 002012 Firm Name: PAPPAS & FODERA ELECT'L
Firm Phone: 718-634-2211  Firm Address: 260 BEACH 116TH ST 2ND FLOOR CORP ROCKAWAY PARK NY 11694 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $158.25
Other Work:   POOL,GARAGE
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: RAMCHAN SUKHOO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    18  10    16               
GND                   
Buildings Total 24  16    19                  
Total Units : 59 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/25/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADDITION WORK THIS IS THE 2ND APP

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A355418
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/23/2017 08/25/2017 GBZ V (14) (6)
INSPECTION COMMENTS: GROUNDING FOR POOL NOT YET VERIFIED, NEED TO INSPECT
 
(2) 10/03/2017 10/04/2017 WYF C R (33) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A355418
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (130) NO GROUND ROD FOR REMOTE BUILDING
(OPEN SPACE) NO GROUND ROD PROVIDED FOR GARAGE PANEL
RSLV 08/23/2017 08/23/2017 10/03/2017
 
002 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(OPEN SPACE) LOCKNUT LOOSE IN GARAGE PANEL
RSLV 08/23/2017 08/23/2017 10/03/2017
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(OPEN SPACE) GFCI NOT PROVIDED FOR GARAGE RECEPTACLES
RSLV 08/23/2017 08/23/2017 10/03/2017
 
004 (999) OTHER
(OPEN SPACE) NO DISCONNECT FOR GARAGE PANEL ART 225.31
RSLV 08/23/2017 08/23/2017 10/03/2017
 
005 (999) OTHER
(OPEN SPACE) SWITCHED LIGHT FOR SIDE DOOR GARAGE ART 210.70A2B
RSLV 08/23/2017 08/23/2017 10/03/2017
 
006 (999) OTHER
(OPEN SPACE) 3/4" PVC FOR GARAGE PANEL NOT SECURE
RSLV 08/23/2017 08/23/2017 10/03/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back