Electrical Application Details for App #: A354979
Premises: 41-32 27 STREET QUEENS BIN: 4005015     Block: 415   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41-32 27 ST Census Tract:   33 Health Area:  0710
CEL,ROF 001 THRU 015 Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11101 Community Board:   401
Related Job Number:    420650110
DOB Cross Street(s):    41 AVENUE,    QUEENS PLAZA NORTH
Status:   C - JOB IS SIGNED OFF 03/03/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/19/2016 4:25 PM
Application Entered:   10/19/2016 Job Start Date:   10/19/2016
Last Change:   03/03/2020 Job End Date:   10/19/2017
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     02/18/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012324 Licensee Name: GERBERT BONHOMME
Firm: 004105 Firm Name: SUPREME ELECTRIC CORP
Firm Phone: 718-658-1078  Firm Address: 107-54 SUTPHIN BLVD JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $1,536.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420650110
Building Used As:   Z - Other
Store / Other:   D3-ELEVATOR APT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELIRAN MALOUL
Owner Business Name: KAKIMIAN ORGANIZATIO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  47  10/20 MAIN BREAKER PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  3 PHASE 60 AMP MOTOR
B. Each Additional 10 Floors Or Less  2  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  ABC  36  45  21               
003  ABC  36  45  21               
004  ABC  36  45  21               
005  ABC  36  45  21               
006  ABC  36  45  21               
007  ABC  36  45  21               
008  ABC  36  45  21               
009  ABC  36  45  21               
010  ABC  36  45  21               
011  ABCD  36  45  21               
012  ABCD  36  45  21               
013  ABCD  36  45  21               
014  ABCD  36  45  21               
015  ABCD  36  45  21               
Buildings Total 504  630  84  294                  
Total Units : 1512 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 47 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 49 - Removed Meters 0 = Total Meters 49

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/19/2016 Notice: C - CALL TO OFFICE 02/08/2020
Power Issued: 10/19/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  COMPLETE WIRING OF APARTMENT COMPLEX. SERVICE WORK WIL BE UNDEER A DIFFERENT PERMIT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A354979
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/25/2019 11/26/2019 JRP V (145) (1)
INSPECTION COMMENTS: ALL APARTMENTS INSPECTED ONLY. INSTALLATION OF ELEVATOR DISCONNECT (LINE SIDE) ONLY
 
(2) 12/10/2019 12/11/2019 GBZ V R (50) (2)
INSPECTION COMMENTS: FAIL BOXES IN WOOD WALLS NOT FLUSH WITH WOOD T OUT, FACE PLATES DON'T COVER OPENING COMPLETELY
 
(3) 02/08/2020 02/08/2020 EVG J X (98) (0) Y
INSPECTION COMMENTS: JOB IS IN PROGRESS, CONTRACTOR NEEDS TO AMEND APPLICATION TO TO SHOW SVC SWITCH AND FEEDERS FOR ALL APARTMENTS.
 
(4) 02/18/2020 02/18/2020 EVG C R (51) (0)
INSPECTION COMMENTS: JOB PASSED.

OBJECTION FOR APPLICATION #: A354979
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)IN ALL HALLWAYS IGNITABLE MATERIAL AROUND RECEPTACLES , NO FLUSH.314.20
RSLV 11/25/2019 11/25/2019 12/10/2019
 
002 (999) OTHER
(ALL FLOORS)ALL OUTLET BOXES MOUNTED IN FLAMMABLE MATERIAL IN HALLWAYS SHALL BEFLUSH ART. 314.20
RSLV 12/10/2019 12/10/2019 02/18/2020
 
003 (999) OTHER
(GROUND FLOOR) FACEPLATES TO COVER OPENINGS ART. 406.5
RSLV 12/10/2019 12/10/2019 02/18/2020