| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
1 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT) USED HIGH VOLTAGE COLORS IN THE 208 BOILER PANEL. |
RSLV |
12/19/2018 |
12/19/2018 |
01/09/2019 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) PANEL HAS OPENED SPACES THAT NEED TO BE FILLED. |
RSLV |
12/19/2018 |
12/19/2018 |
01/09/2019 |
| |
| 003 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT)1 1/4 EMT FROM THE PANEL TO THE BOILER UNIT IS NOT SUPPORTED. |
RSLV |
12/19/2018 |
12/19/2018 |
02/26/2019 |
| |
| 004 |
(999) |
OTHER (BASEMENT)250.110, THERE IS NO GROUND CONNECTED TO THE BOILER OR ITS CONTROLPANEL. |
RSLV |
12/19/2018 |
12/19/2018 |
01/09/2019 |
| |
| 005 |
(999) |
OTHER (BASEMENT)210.4, MULTI WIRE BRANCH CIRCUITS NEED HANDLE TIES OR MULTI POLEBREAKERS. |
RSLV |
12/19/2018 |
12/19/2018 |
01/09/2019 |
| |
| 006 |
(999) |
OTHER (BASEMENT) GREEN WIRE USED OFF 30 AMP BREAKER 250.119 |
RSLV |
01/09/2019 |
01/09/2019 |
02/26/2019 |
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)BOILER ROOM EMT SUPPORT CLAMP NOT OF ELECTRICAL MATERIAL (CURRENTLYSTEAM PIPE CLAMP) 110.3B |
RSLV |
02/26/2019 |
02/26/2019 |
04/04/2019 |