Electrical Application Details for App #: A354808
Premises: 142-20 FRANKLIN AVENUE QUEENS BIN: 4117051     Block: 5182   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 142-20 FRANKLIN AV Census Tract:   857 Health Area:  1200
CEL Admin Area:   A - QUEENS Inspection Area:   B
QUEENS, NY 11355 Community Board:   407
DOB Cross Street(s):   UNION STREET,    BOWNE STREET
Status:   C - JOB IS SIGNED OFF 04/15/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/14/2016 12:42 PM
Application Entered:   10/14/2016 Job Start Date:   10/14/2016
Last Change:   04/15/2019 Job End Date:   10/11/2017
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     04/04/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012302 Licensee Name: MAYER WEBER
Firm: 004699 Firm Name: COUNTY ELECL CONTRACTOR I
Firm Phone: 718-964-6090  Firm Address: 207 VAN BRUNT STREET BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
9 - OTHER
Total Fee:  $52.00
Other Work:   MOBILE BOILER TEMP
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: FAIRMONT 88 LLC
Authorized Representative:  R BAUER
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                     
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/26/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A354808
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/19/2018 12/19/2018 EVG V (50) (5)
INSPECTION COMMENTS: JOB FAILED.
 
(2) 01/09/2019 01/09/2019 STP V Y (25) (1)
INSPECTION COMMENTS: FAIL.
 
(3) 02/26/2019 02/26/2019 JUY V R (45) (1)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(4) 04/04/2019 04/04/2019 EVG C R (46) (0)
INSPECTION COMMENTS: JOB PASSED.

OBJECTION FOR APPLICATION #: A354808
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) USED HIGH VOLTAGE COLORS IN THE 208 BOILER PANEL.
RSLV 12/19/2018 12/19/2018 01/09/2019
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) PANEL HAS OPENED SPACES THAT NEED TO BE FILLED.
RSLV 12/19/2018 12/19/2018 01/09/2019
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT)1 1/4 EMT FROM THE PANEL TO THE BOILER UNIT IS NOT SUPPORTED.
RSLV 12/19/2018 12/19/2018 02/26/2019
 
004 (999) OTHER
(BASEMENT)250.110, THERE IS NO GROUND CONNECTED TO THE BOILER OR ITS CONTROLPANEL.
RSLV 12/19/2018 12/19/2018 01/09/2019
 
005 (999) OTHER
(BASEMENT)210.4, MULTI WIRE BRANCH CIRCUITS NEED HANDLE TIES OR MULTI POLEBREAKERS.
RSLV 12/19/2018 12/19/2018 01/09/2019
 
006 (999) OTHER
(BASEMENT) GREEN WIRE USED OFF 30 AMP BREAKER 250.119
RSLV 01/09/2019 01/09/2019 02/26/2019
 
007 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR)BOILER ROOM EMT SUPPORT CLAMP NOT OF ELECTRICAL MATERIAL (CURRENTLYSTEAM PIPE CLAMP) 110.3B
RSLV 02/26/2019 02/26/2019 04/04/2019