| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
3 |
|
| B. 101 Up to 200 AMPS |
1 |
125A 30CKT |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
2/3 & 4/3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
125A 20CKT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
125A 24CKT & 100A 30CK |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 001) BEDROOM AFCI DEFECTIVE |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 001) BATHROOM LIGHTS & FAN DO NOT WORK |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 003 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 001) NOT SPECIFIC |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 002) REAR BEDR. CLOSET LIGHT BOX |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 005 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 002) AT RAILING NEXT TO STAIRS |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 006 |
(999) |
OTHER (FLOOR: 002) NO BALCONY RECEPTACLE 210.52(E)(3) |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 007 |
(999) |
OTHER (FLOOR: 003) HOOD POWER NOT TERMINATED IN CABINET ABOVE 300.15 |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 008 |
(218) |
UNAPPROVED FIXTURES INSTALLED IN ALL CLOTHES CLOSETS (ALL FLOORS) - |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 009 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT (ALL FLOORS) 1ST & 3FL PANELS |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 010 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (BASEMENT) BOILER ROOM RECES. & LAUNDRY RECES WITIN6' |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 011 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT) BOILER ROOM |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 012 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (OPEN SPACE) A/C UNITS OUTSIDE ON 30A CIRCUIT HAS NO EGC |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 013 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (OPEN SPACE) BX EXPOSED BEHIND A/C UNITS |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |
| |
| 014 |
(999) |
OTHER (OPEN SPACE) A/C UNITS: LFMC NOT SECURED 350.30 |
RSLV |
04/19/2017 |
04/19/2017 |
08/21/2017 |