| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
#6/3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
125A 14CRT |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (FLOOR: 002) #14AWG GROUNDING BONDING IN USE |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002) NEUTRAL BRIDGE BETW. NEUTRAL BARS UNDERSIZED |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002) DEVICES PIGTAILED WITH #14AWG WIRE |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 004 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 002) - |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) LFNC USED AT AC |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) ROMEX USED BETWEEN A/H & A/C UNIT |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 007 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 002) OUTSIDE AC GFCI |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 002) 2R |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 009 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (FLOOR: 002) OUTSIDE AT AC |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 010 |
(999) |
OTHER (FLOOR: 002) #14AWG CONDUCTORS USED FOR AC POWER |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 011 |
(999) |
OTHER (FLOOR: 002) NO BREAKER TIE ON MULTI-WIRE CIRCUITS 210.4 |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 012 |
(999) |
OTHER (FLOOR: 002) A/C OVER FUSED 440.22(C) |
OPEN |
09/16/2016 |
09/16/2016 |
|
| |
| 013 |
(999) |
OTHER (FLOOR: 002) DEVICES LOOSE IN BOXES |
OPEN |
09/16/2016 |
09/16/2016 |
|