BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A351315
Premises: 25-20 41 AVENUE QUEENS BIN: 4436801     Block: 415   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41-04 27 ST Census Tract:   33 Health Area:  0710
ENTIRE BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11101 Community Board:   401
Related Job Number:    420887570
DOB Cross Street(s):    41 AVENUE,    QUEENS PLAZA NORTH
Status:   C - JOB IS SIGNED OFF 12/06/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/18/2016 10:41 AM
Application Entered:   07/18/2016 Job Start Date:   07/18/2016
Last Change:   12/06/2017 Job End Date:   07/18/2017
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     12/06/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012398 Licensee Name: WEN BIN CEN
Firm: 004190 Firm Name: R & T ELECTRICAL CORP
Firm Phone: 718-526-6888  Firm Address: 36-03B COLLEGE POINT BLVD BSMNT FLUSHING NY 11354 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $2,957.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420887570
Building Used As:   Z - Commercial/Residential (5  Stores, 32 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: XI ZHAO
Owner Business Name: CH41LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  4SETS 350MCM
D. 601 Up to 1200 AMPS  2  4SETS 500MCM
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  32  100AMPS #2 WIRE
B. Over #2 to 1/0  3  100AMPS #3WIRE
C. Over 1/0 to 250 MCM  2  200AMPS #3/0
D. Over 250 MCM  8  4SETS500MCM AND 4SETS350M
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  32  10-20 CIRCUIT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  2/200AMPS AND 3/100AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  24 VOLT'S

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  3COM  15  15  15         
001  2COM  10  15  10         
002  ABCD  20  50  20  20         
003  ABCD  20  50  20  20         
004  ABCD  20  50  20  20         
005  ABCD  20  50  20  20         
006  ABCD  20  50  20  20         
007  ABCD  20  50  20  20         
008  ABCD  20  50  20  20         
009  ABCD  20  50  20  20         
Buildings Total 185  430  37  165  185     30           
Total Units : 1032 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 32 #4-Wire 6 #10-Wire 1
Existing Meters 0 + New Meters 39 - Removed Meters 0 = Total Meters 39

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/18/2016 Notice: 1 - FIRST NOTICE 11/24/2017
Power Issued: 07/18/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BUILDING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A351315
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/24/2017 11/24/2017 GBZ V (65) (5)
INSPECTION COMMENTS: INSPECTED SERVICE AND PART OF ROOF NEED FULL INSPECTION FOR APTS AND ALL AC UNITS
 
(2) 12/06/2017 12/06/2017 WYF C R (60) (0)
INSPECTION COMMENTS: INSPECTION PASSED

OBJECTION FOR APPLICATION #: A351315
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(ROOF) WATER HEATER ROOM INSUFFICENT ACCESS TO SERVICE SWITCHES
RSLV 11/24/2017 11/24/2017 12/06/2017
 
002 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(ROOF) ALL SEAL TIGHT CONNECTORS LOOSE
RSLV 11/24/2017 11/24/2017 12/06/2017
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) EMT NOT SECURE IN WATER HEATER ROOM
RSLV 11/24/2017 11/24/2017 12/06/2017
 
004 (999) OTHER
(ROOF) ALL SEAL TIGHT FOR AC UNITS NOT UL LISTED ART 350.6
RSLV 11/24/2017 11/24/2017 12/06/2017
 
005 (999) OTHER
(ROOF) IN USE COVER BROKEN ART 110.3
RSLV 11/24/2017 11/24/2017 12/06/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.