BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A350812
Premises: 27-21 44 DRIVE QUEENS BIN: 4596127     Block: 268   Lot: 4
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 27-21 44 DR Census Tract:   19
GROUND Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    420652537
DOB Cross Street(s):   JACKSON AVENUE,    THOMSON AVENUE
Status:   C - JOB IS SIGNED OFF 03/10/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/30/2016 Job Start Date:   06/23/2016
Last Change:   03/10/2018 Job End Date:   06/23/2019
Appointment Status:   
Last Inspection By:   BASDEO, C       On     03/08/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012183 Licensee Name: PATRICK J KENNELLY
Firm: 000138 Firm Name: ANTHONY G FERRY INC
Firm Phone: 646-678-3795  Firm Address: 314 CITY ISLAND AVENUE BRONX NY 10464 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420652537
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   535503     Submittal #: 16A0055  
Owner / Occup: DAVID SJAUW
Owner Business Name: S2 CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-600A
D. 601 Up to 1200 AMPS  3  1-1200A, 2-800A
E. Over 1200 AMPS  1  1-2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  2-4/0
D. Over 250 MCM  24  3-500MCM,6-600MCM,15-750M
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  120  120-150A
C. 3 Phase Up to 225 AMPS  15  14-100A,1-225A
D. 3 Phase Over 225 AMPS  4  1-400A,1-600A,1-800A,1-12
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    70  25    25  70             
GND    110  75    25  110             
002    110  115  15  110  110             
003    110  115  10  110  110             
004    110  115  15  110  110             
005    110  115  15  110  110             
006    110  115  15  110  110             
007    110  115  15  110  110             
008    110  115  15  110  110             
009    110  115  15  110  110             
010    110  115  15  110  110             
011    110  115  15  110  110             
012    110  115  15  110  110             
013    110  115  15  110  110             
014    110  115  15  110  110             
015    110  115  10  110  110             
016    110  115  12  110  110             
017    110  115  12  110  110             
018    110  115  12  110  110             
019    110  115  12  110  110             
020    110  115  12  110  110             
021    110  115  12  110  110             
022    110  115  12  110  110             
023    110  115  12  110  110             
024    110  115  12  110  110             
025    110  115  12  110  110             
026    110  115  110  110             
Buildings Total 2930  2975  328  2800  2930                
Total Units : 11963 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 3
Existing Meters 0 + New Meters 125 - Removed Meters 0 = Total Meters 125

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/30/2016 Notice: C - CALL TO OFFICE 02/27/2018
Power Issued: 06/30/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A350812
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/12/2018 01/12/2018 COB V (230) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 02/27/2018 02/27/2018 COB J X (36) (0) Y
INSPECTION COMMENTS: OBJECTIONS REMOVED, CONTRACTOR TO FILE FOR GENERATOR AND HVAC UNITS
 
(3) 03/08/2018 03/08/2018 COB C R (5) (0)
INSPECTION COMMENTS: CERTIFY REFERENCE Q00023524 FOR ADDITIONAL DETAILS

OBJECTION FOR APPLICATION #: A350812
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(GROUND FLOOR)SERVICE ROOM, INSTALLATION NOT TO PRINT, LAYOUT MISSING SERVICE PULLBOX
RSLV 01/12/2018 01/12/2018 03/08/2018
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(GROUND FLOOR)SERVICE ROOM, ONE LINE DIAGRAM MISSING SETS OF CONDUCTORS TO SERVICESWITCH #3
RSLV 01/12/2018 01/12/2018 03/08/2018
 
003 (999) OTHER
(GROUND FLOOR)SERVICE ROOM, PANIC BAR NOT PROVIDED FOR SERVICE ROOM DOOR
RSLV 01/12/2018 01/12/2018 03/08/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order